5. Installaon Instrucons – Recommended Locaons
When wall-mounng place the alarm a horizontal distance of between 1 metre and 3 metres from a fuel
burning appliance.
Wall-mounted alarms should be close to the ceiling, but at least 150mm away to avoid being in ‘dead-air’ space.
Locate within hearing distance of bedrooms* and place at sleeping height if a heang appliance is in the
bedroom.
CO alarms in rooms with sloped ceilings should be located on the high side of the room.
Ceiling mounted alarms should be at least 300 mm from any wall.
If there is a paron in the room, locate the alarm on the same side of the paron as the potenal source.
*A CO alarm should be installed in all rooms containing a fuel burning appliance. Addional CO alarms should be
installed in rooms where most awake me is spent, in every sleeping area, and on every level of the home.
Locaons to Avoid
Avoid locang next to draughts, such as doors, windows, extractor fans, air vents or other
similar venlaon openings.
Avoid locang close to obstrucons (e.g. behind curtains, shelves or furniture).
Avoid dusty, dirty or greasy areas, such as garages or workshops
Avoid humid (bathrooms), cold (< -10
o
C) or hot (> 40
o
C) or damp areas and keep away from sinks.
2539-7201-05_10LLCO_10LLDCO_V1:_ 2016.11.2 9:06 AM Page 9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde 10LLDCO and is the answer not in the manual?

Kidde 10LLDCO Specifications

General IconGeneral
BrandKidde
Model10LLDCO
CategorySecurity System
LanguageEnglish

Related product manuals