8. Alarm Visual and Audible Indicators
If you require further information please contact Product Support at 1-800-880-6788 or write
us at: Kidde Canada Inc., P.O. Box 40, Apsley, ON K0L 1A0 or visit us on the web at
www.kiddecanada.com.
Operational Mode
Visual
Indications
Audible
Indications Note:
Initiating Alarm
(Multiple alarms in
an Interconnected
system)
Green LED blinks once per
second indicating that this
is the unit initiating the
alarm in an interconnected,
multiple alarm, system.
Red LED blink in time
with alarm pattern.
Strobe will flash 1 time
per second if AC power
is applied.
3 long beeps, voice mes-
sage “Fire! Feu!”,3 long
beeps, repeating.
Green LED operation of
non-initiating alarms:
AC power applied: On
continuously.
DC Only power applied:
Flash once every minute.
All P4010ACLEDSCOCA
strobes in an
interconnected system will
flash in synchronization.
Smoke or CO Alarm
Memory
Red LED blinks once
every 16 seconds.
None Pressing the Test/Hush
button (dome) clears
alarm memory.
Low Battery Amber LED blink 2 times
per second – AC Power
applied
Red LED blink in time
with unit chirp every
60s. Battery backup
(DC only).
AC Power applied – Unit
will chirp once a minute
followed by the voice
message “Low Battery.
Pile Faible”
Battery Backup – Unit
will chirp once a minute,
the voice message “Low
Battery. Pile Faible”
will occur once every
15 minutes.
Ambient Light Sensor
Feature – Inhibits Low
Battery chirps during
the night.
The alarm should be
replaced within 7 days
of low battery. See
Discharging/Killing The
Battery section before
disposing of alarm.
Fault Mode Red LED will blink in time
with unit chirp every 30
seconds. Separate from
the fault blink, the amber
LED will also flash a fault
code every 30 seconds.
The fault code can be 2 to
14 flashes depending on
the fault type.
Unit will chirp every
30 seconds.
See Maintenance
section.
End of Unit Life Red LED blinks in time
with unit chirp, 2 times
every 30 seconds.
Unit will chirp 2 times
every 30 seconds.
Ambient Light Sensor -
Inhibits End of Unit Life
chirps at night for the
first 30 days of the End of
Unit Life period.
Remove, discharge, and
replace alarm as soon as
possible.”
End of Unit Life, Hush
Mode
Red LED blinks once
every 2 seconds.
None, End of Unit Life
chirps silenced.
Pressing the Test/Hush
button (dome) will silence
the chirps for 3 days at a
time for a maximum of 30
days. After 30 days, End
of Unit Life chirps cannot
be silenced.
Remove, discharge, and
replace alarm as soon as
possible.
End of Unit Life,
(30 days after End of
Life chirps begin)
Red LED will blink in time
with unit chirp 2 times
every 30 seconds.
Unit will chirp 2 times
every 30 seconds.
Remove, discharge, and
replace alarm as soon as
possible.