TP-6109 6/0318 Section 2 Operation
2.8.4 Fault Shutdowns
The generator set shuts down automatically under the
following fault conditions and cannot be restarted until
the fault condition is corrected. The system automatically
resets when the problem is corrected or the generator
set cools (if high engine temperature was the fault).
Fault Description
High engine
temperature
Shutdown occurs 5 seconds after
the fault. The high engine
temperature shutdown does not
function during the first 5 seconds
after startup.
NOTE: The high temperature
shutdown functions only when the
coolant level is in the operating
range.
High exhaust
temperature
Shutdown occurs 5 seconds after
the fault. The high exhaust
temperature shutdown does not
function during the first 5 seconds
after startup.
Low coolant level Shutdown occurs 5 seconds after
the fault. Low coolant level
shutdown does not function during
the first 5 seconds after startup.
Low oil pressure Shutdown occurs 5 seconds after
the fault. Low oil pressure
shutdown does not function during
the first 5 seconds after startup.
NOTE: The low oil pressure
shutdown does not protect against
low oil level. Check the oil level at
the engine.
Overcrank Shutdown occurs after 30 seconds
of continuous cranking. Shutdown
occurs after 30 seconds if the
engine or starter does not turn
(locked rotor).
Overspeed Shutdown occurs immediately
when the governed frequency on
50 and 60 Hz models exceeds
70 Hz.
x:op:004:005
2.8.5 Controller Resetting Procedure
(Following Fault Shutdown)
Use the following procedure to restart the generator set
after a fault shutdown.
1. Disconnect the generator set from the load using
the line circuit breaker or automatic transfer switch.
See the Safety Precautions at the beginning of this
section before proceeding.
2. Correct the cause of the fault shutdown. See the
Safety Precautions at the beginning of this section
before proceeding.
3. Start the generator set by moving the generator set
master switch to RESET/OFF and then to RUN.
4. Verify that the cause of the shutdown has been
corrected by test operating the generator set.
5. Reconnect the generator set to the load using the
line circuit breaker or automatic transfer switch.
6. Move the generator set master switch to the AUTO
position for startup by remote transfer switch or
remote start/stop switch.
x:op:004:006