CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E Page 106
BMS ADRESS TABLES
ModBus, Trend, BACnet & Carel
Logical
@ (hexa)
[On / Off] Unit 3111
02H 2 R/W
[Reset] Discharges the safety measures of the unit 3112
03H 3 R/W
[Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, [On] the
blower is running.
3351
(BMS)
04H 4 R/W
[Enable] Stopping and running of the fan in the "Control Dead Zone". [Off] the blower
is stopped, [On] the blower is running.
3352
(BMS)
05H 5 R/W
[BMS] Activation of the Unoccupied mode [Off] Occupied mode - [On] Unoccupied
mode
3935
06H 6 R/W
[Room regulation] Choices of the priority of regulation in Heating - [Off] Heat Pump
then Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat
Pump
3324
(BMS)
07H 7 R/W
[F-Air Reheat] Activate reheating of the fresh air in the dead zone to maintain supply
temperature.
3331
(BMS)
08H 8 R/W
[F-Air Reheat] Choices of the priority of regulation in Heating - [Off] Heat Pump then
Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
[Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped.
3353
(BMS)
0AH 10 R/W
[Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, [Off] Stop the
CO2 control on a zone.
3354
(BMS)
0BH 11 R/W
[Enable] [OFF] Force the unloading of compressors in cooling mode.
3355
(BMS)
0CH 12 R/W
[Enable] [OFF] Force the unloading of compressors in heating mode.
3356
(BMS)
0DH 13 R/W
[Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil)
[Enable] [OFF] Force the unloading of humidity control.
3358
(BMS)
0FH 15 R/W
[Unloaded] Force the stop of half of the compressors moving has the moment of the
activation of this point.
3643
10H 16 R/W
[Clock] [OFF] read hour & minute [ON] write hour & minute …
11H 17 R/W
[Dry contact] Digital Output, Free 1, BM50-J17-NO12 2141
12H 18 R/W
[Dry contact] Digital Output, Free 2, BE50-J5-NO1 2142
13H 19 R/W
[Dry contact] Digital Output, Free 3, BE50-J6-NO2 2143
14H 20 R/W
[Dry contact] Digital Output, Free 4, BE50-J7-NO3 2144
15H 21 R/W
[Dry contact] Digital Output, Free 5, BE50-J8-NO4 2145
16H 22 R/W