EasyManuals Logo
Home>Lennox>Air Conditioner>BAH035SNM

Lennox BAH035SNM User Manual

Lennox BAH035SNM
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
VENTILATION: FILTERS
BALTIC R410A-IOM-0708-E Page 71
FILTER REPLACEMENT
After opening the filter access panel, lift the filter retaining log.
The filters can then be removed and replaced easily by sliding the dirty filters out and clean ones in.
The CLIMATIC controller can monitor the pressure drop across the filter (If option fitted)
The following set points can be adjusted depeding on the installation.
“Airflow in page 3411 = 25Pa by default
“No filter “ in page 3412 = 50Pa by default
“Dirty Filter” in page 3413 = 250Pa by default
The actual pressure drop measured accross the coil can be read on the Climatic Display DS50 in menu 2131
.
The following faults may be identified
-Fault code 0001 AIRFLOW FAILURE, if measured ΔP across the filter and coil is below the value set in page 3411
-Fault code 0004 DIRTY FILTERS, if measured ΔP across the filter and coil is above the value set in page 3413
-Fault code 0005 MISSING FILTERS, if measured ΔP across the filter and coil is below the value set in page 3412
Fig. 43