CLIMATIC 50 ROOFTOP VERSION 23
BALTIC R410A-IOM-0708-E Page 108
Analogical
@ (hexa)
@ (deci)
DS50
01H 1 R/W
1 = 1 s
[ BMS ] Activation of the control by a computer or an automat - mode
BMS is activated if this value is different from zero, This value is
decreased every second
3934
02H 2 R/W
10 = 1.0°c
[Occupation][Room SP] Required maximum room temperature in °C.
Cooling set point
3322
(BMS)
03H 3 R/W
10 = 1.0°c
[Occupation][Room SP] Required minimum room temperature in °C.
Heating set point
3323
(BMS)
04H 4 R/W
10 = 1.0%
[Room SP] Required room minimum fresh air rate in % Middle of the
dead zone.
3312
(BMS)
05H 5 R/W
10 = 1.0°c
[Unoccupied][Room SP] Required maximum room temperature in °C.
Cooling set point
3322
(Uno)
06H 6 R/W
10 = 1.0°c
[Unoccupied][Room SP] Required minimum room temperature in °C.
Heating set point
3323
(Uno)
07H 7 R/W
10 = 1.0%
[Humidity] Desired Maximum relative humidity in Room (in %).
Dehumidification set point.
3341
(BMS)
08H 8 R/W
10 = 1.0%
[Humidity] Desired Minimum relative humidity in Room (in %).
Humidification set point.
3342
(BMS)
09H 9 R/W
not used
0AH 10 R/W
not used
0BH 11 R/W
not used
0CH 12 R/W
1 = 1h [Clock] Hour 3121
0DH 13 R/W
1 = 1m [Clock] Minute 3122
0EH 14 R/W
1 = 1 [Clock] Day of the month 3123
0FH 15 R/W
1 = 1 [Clock] Month 3124
10H 16 R/W
1 = 2001 [Clock] Year 3125
11H 17 R/W
10 = 1.0°c [BMS] Room temperature coming from the BMS 2824
12H 18 R/W
10 = 1.0% [BMS] Room humidity coming from the BMS 2828
13H 19 R/W
10 = 1.0°c [BMS] Outdoor temperature coming from the BMS 2814
14H 20 R/W
10 = 1.0% [BMS] Outdoor humidity coming from the BMS 2818
15H 21 R/W
1 = 1 ppm [BMS] Air quality coming from the BMS
16H 22 R/W
not used
17H 23 R/W
not used
18H 24 R/W
not used
19H 25 R/W
not used
1AH 26 R/W
not used
1BH 27 R/W
not used
1CH 28 R/W
not used
1DH 29 R/W
not used
1EH 30 R/W
not used
1FH 31 R/W
not used
20H 32 R/W
not used
21H 33 R 1 = 1 [Alarm] Code Error 1000
22H 34 R 10 = 1.0°c [Temperature] Room 2112
23H 35 R 10 = 1.0°c [Temperature] Outdoor 2111