[Absolute Humidity] Outdoor 2123
2AH 42 R 1 = 1 pa [Flow] Differential pressure on the air, in Pascal 2131
2BH 43 R 1 = 1 ppm [CO²] Level in ppm 2132
2CH 44 R 10 = 1.0% [% of opening] Damper of fresh air 2413
2DH 45 R 10 = 1.0% [% of opening] Valve gas 2618
2EH 46 R 10 = 1.0% [% of opening] Electrical heaters (Triac) 2627
2FH 47 R 10 = 1.0% [% of opening] Hot water coil 2633
30H 48 R 10 = 1.0% [% of opening] Humidifier 2714
31H 49 R 10 = 1.0°c [Dry contact] Temperature, Free 1, BE50-J9-B1 2161
32H 50 R 10 = 1.0°c [Dry contact] Temperature, Free 2, BE50-J9-B2 2162
33H 51 R 10 = 1.0°c [Dry contact] Temperature, Free 3, BE50-J10-B3 2163
34H 52 R 10 = 1.0°c [Dry contact] Temperature, Free 4, BE50-J10-B4 2164
35H 53 R 10 = 1.0% [Dry contact] Humidity, Free 1, BE50-J9-B1 2165
36H 54 R 10 = 1.0% [Dry contact] Humidity, Free 2, BE50-J9-B2 2166
37H 55 R 10 = 1.0% [Dry contact] Humidity, Free 3, BE50-J10-B3 2167
38H 56 R 10 = 1.0% [Dry contact] Humidity, Free 4, BE50-J10-B4 2168
39H 57 R 1 = 1 h [Running Time, Count] Fan, Blower 2318
3AH 58 R 1 = 1 h [Running Time, Count] Compressor, 1 2519
3BH 59 R 1 = 1 h [Running Time, Count] Compressor, 2 2529
3CH 60 R 1 = 1 h [Running Time, Count] Compressor, 3 2539
3DH 61 R 1 = 1 h [Running Time, Count] Compressor, 4 2549
3EH 62 R bit
[Alarm]
bit.0 = Air Flow
bit.1 = Dirty Filters
bit.2 = No Filters
bit.3 = Electrical heaters
bit.4 = High Temperature, Supply
bit.5 = Low Temperature, Room
bit.6 = Gas Burner 1
bit.7 = Gas Burner 2
bit.8 = Low Temperature, Supply
bit.9 = High Temperature, Room
bit.10 = Humidifier
bit.11 = Low Humidity, Room
bit.12 = High Humidity, Room
bit.13 = Pump
bit.14 = Real Time Clock
bit.15 = BE50
…