BALTIC R410A-IOM-0708-E Page 62
PERFORMANCES
ACCESSORIES PRESSURE DROPS
BAC = Cooling only rooftop
BAH = Heat pump rooftop
BAG = Cooling only rooftop with gas fired heating
BAM = Heat pump rooftop with gas fired heating
Economiser
EU4
Filters
F7
Filters
Water
Coil
Hot Electric heater
(Pa)
Roofcurb
Multi
directional
Heat
Recovery
module
Size Airflow
(Pa) (Pa) (Pa) (Pa) S M H (Pa) (Pa)
Fresh
(1)
2900 18 0 39 31 57 58 60 16 23 108 69
3600 28 6 66 46 105 107 109 24 35 161 105
020
4300 39 12 98 61 146 149 151 35 50 226 151
3600 28 6 66 46 75 77 79 24 35 161 105
4500 43 14 108 66 133 135 138 38 55 247 165
030
5400 62 25 160 89 187 190 193 55 79 352 238
5000 22 5 62 51 75 78 81 25 24 149 105
6300 36 14 104 76 134 138 141 39 38 230 167
035
7600 52 24 155 105 189 193 197 58 56 331 243
6500 23 3 52 56 81 85 89 20 29 113 80
8100 36 10 86 82 141 145 150 32 45 170 124
045
9700 51 18 127 113 196 201 207 46 64 239 177
7200 28 6 66 67 94 98 102 25 35 136 98
9000 44 14 108 99 160 165 170 39 55 207 153
055
10800 63 25 160 136 224 230 236 56 80 293 220
8600 16 3 50 58 62 67 72 19 12 129 91
11500 29 12 96 90 112 119 125 33 37 223 162
065
13000 37 18 125 119 152 159 167 43 26 282 207
9 950 22 7 70 75 74 79 85 25 16 171 123
13500 35 16 117 113 128 135 142 40 25 204 223
075
14000 56 31 194 172 186 195 204 65 40 326 240