Page 19
TABLE 8– ELECTRIC HEAT DATA (1 PHASE) – CB30M–41 & CB30M–46
Blower Coil
Electric Heat kW,
Model Number
Number of
Volts
kW
Btuh
Blower
Motor
{Minimum
Circuit Ampacity
& Shipping Weight
Amps
Circuit 1 Circuit 2
b 208/230v–1 ph b
ECB29-5
208 3.8 12,800 1.73 25 – – – –
(28K31)
220 4.2 14,300 1.73 26 – – – –
-
(28K32)
230 4.6 15,700 1.73 27 – – – –
4 lbs. (2 kg)
240 5.0 17,100 1.73 28 – – – –
ECB29-8
208 6.0 20,500 1.73 38 – – – –
(28K33)
220 6.7 22,900 1.73 40 – – – –
-
(28K34)
230 7.3 25,100 1.73 42 – – – –
5 lbs. (2 kg)
240 8.0 27,300 1.73 44 – – – –
ECB29-10
208 7.5 25,600 1.73 47 – – – –
(28K35)
220 8.4 28,700 1.73 50 – – – –
-
(28K36)
230 9.2 31,400 1.73 52 – – – –
5 lbs. (2 kg)
240 10.0 34,100 1.73 54 – – – –
-
208 9.4 32,000 1.73 21 38
ECB29-12.5CB
220 10.5 35,800 1.73 22 40
.
10 lbs. (5 kg)
230 11.5 39,200 1.73 23 42
240 12.5 42,600 1.73 24 43
208 11.3 38,400 1.73 25 45
ECB29-15CB
220 12.6 43,000 1.73 26 48
10 lbs. (5 kg)
230 13.5 47,000 1.73 27 50
240 15.0 51,200 1.73 28 52
208 15.0 51,200 1.73 47 45
ECB29-20CB
220 16.8 57,300 1.73 50 48
14 lbs. (6 kg)
230 18.4 62,700 1.73 52 50
240 20.0 68,200 1.73 54 52
ECB29-5
208 3.8 12,800 2.4 26 – – – –
(28K31)
220 4.2 14,300 2.4 27 – – – –
-
(28K32)
230 4.6 15,700 2.4 28 – – – –
4 lbs. (2 kg)
240 5.0 17,100 2.4 29 – – – –
ECB29-8
208 6.0 20,500 2.4 39 – – – –
(28K33)
220 6.7 22,900 2.4 41 – – – –
-
(28K34)
230 7.3 25,100 2.4 43 – – – –
5 lbs. (2 kg)
240 8.0 27,300 2.4 45 – – – –
ECB29-10
208 7.5 25,600 2.4 48 – – – –
(28K35)
220 8.4 28,700 2.4 51 – – – –
-
(28K36)
230 9.2 31,400 2.4 53 – – – –
CB30M-46
5 lbs. (2 kg)
240 10.0 34,100 2.4 55 – – – –
CB30U-41/46
208 9.4 32,000 2.4 22 38
ECB29-12.5CB
220 10.5 35,800 2.4 23 40
.
10 lbs. (5 kg)
230 11.5 39,200 2.4 24 42
240 12.5 42,600 2.4 25 43
208 11.3 38,400 2.4 26 45
ECB29-15CB
220 12.6 43,000 2.4 27 48
10 lbs. (5 kg)
230 13.5 47,000 2.4 28 50
240 15.0 51,200 2.4 29 52
208 15.0 51,200 2.4 48 45
ECB29-20CB
220 16.8 57,300 2.4 51 48
14 lbs. (6 kg)
230 18.4 62,700 2.4 53 50
240 20.0 68,200 2.4 55 52
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75_C).
Electric heater capacity only — does not include additional blower motor heat capacity.Minimum circuit ampacity for blower motor only.