EasyManuals Logo
Home>Lennox>Fan>COMFAIR HH Series

Lennox COMFAIR HH Series Application Guide

Lennox COMFAIR HH Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
• 5 •
10 20 30 40 50 60 70
3640 7050 9200 10600 13100 27800 50600
3130 6063 7912 9116 11266 23908 43516
2870 5640 7360 8630 11000 21100 39500
2,468 4,85 6,33 7,422 9,46 18,146 33,97
4972 8512 11210 12800 16818 32430 60111
4276 7320 9641 11008 14464 27890 51696
626 1213 1582 1823 2253 4782 8703
0,174 0,337 0,441 0,506 0,626 1,328 2,418
24 35,9 33,8 31,9 35,9 34 40
2,4 3,7 3,4 3,3 3,7 3,5 4,1
22,2 31,7 28,9 27,9 33,2 24 30
2,3 3,2 2,9 2,8 3,4 2,4 3,1
8400 14300 18850 21520 28490 54240 100810
7224 12298 16211 18507 24502 46647 86698
722 1230 1621 1850 2450 4664 8670
0,201 0,342 0,45 0,514 0,681 1,296 2,408
18,3 29,6 27,5 26,1 35,6 20,7 27
1,9 3 2,8 2,7 3,6 2,1 2,8
3000 6000 9000 12000 18000
2586 5172 7759 10345 15517
4,56 9,12 13,67 18,23 27,35
4500 9000 12000 18000 24000
3879 7759 10345 15517 20690
6,84 13,67 18,23 27,35 36,46
837 1423 1951 2131 3002 4678 9250
0,233 0,395 0,542 0,592 0,834 1,299 2,569
1360 1360 1200 1207 1382 806 822
68 66 70 69 75 78 81
160 240 320 340 580 1320 2600
0,72 0,97 1,43 1,51 2,58 5,86 11,54
230/1/50
Application Guide COMFAIR HH-AGU-1107-E
TECHNICAL DATA - HH
2 PIPES SYSTEM
COMFAIR HH
Total cooling capacity
(1)
W
Frig/h
Sensible cooling capacity
(1)
W
Frig/h
Heating capacity
(3)
W
kcal/h
Water fl ow
(1) (3)
l/h
l/s
Water pressure drops in cooling
(1)
kPa
mWG.
Water pressure drops in heating
(3)
kPa
mWG.
Heating capacity
(2)
W
kcal/h
Water fl ow
(2)
l/h
l/s
Water pressure drops in heating
(2)
kPa
mWG.
Electrical heater heating capacity
(4)
W
kcal/h
Electrical heater power input
(4)
A
Electrica heater heating capacity
(5)
W
kcal/h
Electrical heater input current
(5)
A
Air fl ow
(6)
m
3
/h
m
3
/s
Fan speed
(6)
rpm
Sound power level
(7)
dB(A)
Motor electrical power
(8)
W
Motor electrical input
(8)
A
Electrical supply V/Ph/Hz
Above mentionned technical data are calculated ar the following operating conditions:
- Maximum fan speed
- Standard unit without ducts (fancoil operating without external back pressure)
(1) Cooling: entering water temperature 7°C, leaving water temperature 12°C, entering air temperature 27°C W.B.; 19°C D.B.
(2) Heating: entering water temperature 50°C, same water fl ow as in cooling, entering air temperature 20°C
(3) Heating: entering water temperature 70°C, leaving water temperature 60°C, entering air temperature 20°C
(4) Electric heaters section SRE - B: electric heaters capacities, lower speed cabling (SRE - B supplied as accessory only)
(5) Electric heaters section SRE - A: electric heaters capacities, high speed cabling (SRE - A supplied as accessory only)
(6) Air fl ow and fan speed: fancoil performances with cleaned fi lter
(7) Sound power level: sound power measured following ISO 23741
(8) Electrical data referred to the maximum available speed

Other manuals for Lennox COMFAIR HH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox COMFAIR HH Series and is the answer not in the manual?

Lennox COMFAIR HH Series Specifications

General IconGeneral
BrandLennox
ModelCOMFAIR HH Series
CategoryFan
LanguageEnglish

Related product manuals