• 24 • Installation - Operation - Maintenance manual (IOM) • AIR COOLED CHILLERS & SPLIT UNITS - 0105-E
6 - OPERATION
6.1 - CLIMATIC CONTROL
cf. See the specific CLIMATIC 50 manual
cf. See the specific «Basic CLIMATIC controller» manual
6.1.1 - Menu Tree - ECOLOGIC range
See «Annexes», page 70 to 78
6.1.2 - Menu Tree - ECOMAX range
See «Annexes», page 79 to 90.
6.1.3 - Connection diagrams - CLIMATIC™ 30
A remote controller is offered as an option.
To install this optional remote controller proceeded as follow :
- Connect exactly as indicated in electrical diagram
- The wire should not exceed 50 m.
The three cables for connection from the keypad to the power board must be kept separate from other
cables, using an individual cable channel; and use shielded cables, with a cross-section of 1 mm
2
.
OPERATION
*
2
1
x 1000
Terminal block
Electrical box at the unit
Remote controller (optional)
Three-lead shielded cable with a cross-section of 1mm
2
* Connection to be made by user MAXIMUM LENGTH 50m