EasyManuals Logo
Home>Lennox>Chiller>ECOLOGIC Series

Lennox ECOLOGIC Series User Manual

Lennox ECOLOGIC Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 0105-E • 43 •
TROUBLESHOOTING - REPAIRS
8.5.1.2 - Description of inspection duties - Liquid chiller with reciprocating compressor(s)
START UP
- Check unit installation
- Check water flow and water circuit ancillaries
- Check safety devices
- Check leaktightness
- Configuration of the microprocessor based management system (if used)
- Verification of operating parameters and unit performance
- Transmission of the machine service log
500 H / 1000 H VISITS
- Post wear in inspection
- Oil acidity test, leak test
- Replacement of the filter-drier cartrides depending on the results of the test above.
- Monitor unit performance and any eventual variations linked to use of the installation.
INSPECTION VISIT
- Leak test
- Operating test with record of measurements taken and functional analysis.
MAJOR TECHNICAL INSPECTION
- Inspection visit
- Acid test
- Oil change if necessary
- Replacement of filter-drier cartridges if necessary
- Check up on the microprocessor based management system (if used)
- Adjustment of safety devices
- Verification of unit interlocks
- Lubrication of bearings / dampers if necessary
15 000 H VISIT
- Major technical inspection
- Inspection of the compressor and replacement of valves, springs and seals (depending on the type of
compressor).
30 000 H VISIT
- Major technical inspection
- Inspection of the compressors with replacement of the valves, springs, seals and gaskets, bearings, oil discharge
valve, piston rings.
- Dimensional inspection of the big ends and gudgeon pins, replacement of parts as required (quotation)
(depending on the type of compressor).
TUBE ANALYSIS
- Inspection of water cooled evaporator and condenser tube bundles with an eddy current test to enable potentially
serious problems to be anticipated.
- Frequency : Every 5 years up to 10 years (depending on the quality of water), then every 3 years.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ECOLOGIC Series and is the answer not in the manual?

Lennox ECOLOGIC Series Specifications

General IconGeneral
BrandLennox
ModelECOLOGIC Series
CategoryChiller
LanguageEnglish

Related product manuals