EL16XC1 SERIES
Electrical Data
208/230V - 60 Hz - 1 ph
Model Numbers
Unit Compressor Condenser Fan
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked Ro
tor Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked Ro
tor Amps
(LRA)
EL16XC1-018 20 11.9 9.0 48.0 1/10 1075 0.7 1.3
EL16XC1-024 25 14.6 10.9 59.3 1/6 825 1.0 1.9
EL16XC1-030 25 17.0 12.8 67.8 1/6 825 1.0 1.9
EL16XC1-036
EL16XC1S036
30 18.0 13.6 79.0 1/6 825 1.0 1.9
EL16XC1-041 30 19.3 14.7 75.0 1/6 825 1.0 1.9
EL16XC1-042 40 23.4 17.9 112.0 1/6 825 1.0 1.9
EL16XC1-047 35 21.9 16.1 105.5 1/3 825 1.8 2.9
EL16XC1-048 40 24.2 18.0 117.0 1/4 825 1.7 3.2
EL16XC1-060 50 29.6 22.2 127.9 1/3 825 1.8 2.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.