Features
Installation Options
Residential
Vented vertical and horizontal
Manufactured (mobile) home
Natural gas (NG) or propane (LP)
Bedrooms
Optional wall-mounted or remote thermostat
Venting
This stove can be vented with Security™ Secure Vent™ pipe*. Coaxial
pipe diameters are 6-5/8” outer and 4” inner. The combustion air for this
stove is drawn from outside the house through the outer DV (direct-vent)
pipe. Room air is not required for combustion.
When planning your installation, select the correct length of vent pipe
for your particular requirements. Determine the minimum clearance to
combustibles from the rear of the unit to the wall. It is also important
to note the thickness of the wall. Before cutting the vent hole through
the wall make sure that ALL vent and termination clearances (see Page
17) will be met.
Electrical
The standard fan motor requires 120 Volts AC for operation. The stove is
not dependent on the fan or an outside electrical supply to operate.
WARNING - Electrical Grounding Instructions - This appliance is
equipped with a three-prong (grounding) plug for your protec-
tion against shock hazard and should be plugged directly into a
properly grounded three-prong receptacle. Do not cut or remove
the grounding prong from this plug.
RATINGS
Epic™ 33 (EPIC33) Epic™ 40 (EPIC40)
NATURAL GAS LP GAS NATURAL GAS LP GAS
Max/Min Input BTUh 0-2,000 Feet
(0-610 M)u
33,000 / 23,000 31,000 / 24,000 40,000 / 27,000 39,000 / 30,000
Manifold Pressure (IN. WC)
3.5 / 1.7 10.0 / 5.4 3.5 / 1.7 10.0 / 5.4
Min. Inlet Pressure (IN. WC)
5.0 11.0 5.0 11.0
P4 Efficiency
w
56.98% 63.58% 63.54% 65.10%
Orifice (DMS) 0-2,000 Feet (0-610 M)u
#36/.106 IN. #52/.064 IN. #31/.120 IN. #49/.073 IN.
uUnit factory equipped for 0-2000 FT/0-610 M, In Canada 0-4500 FT/0-1370 M
vThe Steady State Efficiency numbers based on maximum vent configuration.
wTested to CSA P.4.1-02 “Testing Method for Measuring Annual Fireplace Efficiency.
Electrical Rating: 120 VAC, 60 HZ, Less Than 2 Amps
Millivolt Valve
This stove is operated with a millivolt valve and therefore burns even
during a power outage.
Fuel
This stove comes from the factory equipped to burn natural gas at a
specified elevation. The stove can be converted to burn LP gas (liquid
propane) by changing the cassette (valve and pilot assembly) or installing
a conversion kit. Only Lennox Hearth Products conversion kits can be
used to convert from NG to LP or LP to NG. Contact your Lennox Hearth
Products dealer for details.
Specifications
Pipe:Type - direct-vent
Recommended manufacturer*
Security™ Secure Vent™*
Diameter - 6-5/8”x 4” for all installations
Stove Packaging List
The Epic™ gas stove comes with the following parts:
1 Stove Body with Burner Cassette and 150 CFM Blower
1 3/8”x 9” Gas Pipe
1 3 pc. Brick Panel Set
1 4 pc. Log Set
1 Bag of Ember Material
1 Bag of Rock Wool
1 Bag of Flue Restrictors, Brick Panel Brackets and Tap-tites
1 Power Cord
1 Epic 33 Conversion Orifice
1 Installation and Operation Manual
Options
One required: Black Painted, Gold, Brushed Nickel, or Black Nickel Trim
Kit
* Other approved chimney brand is Simpson Dura-Vent DV-GS.
PRE-INSTALLATION