1.10. MPBMulti-ZoneSpecicationsOutdoorUnits(3-4Ton)
Nominal Size - Tons 3 4
Outdoor Unit Model No. MPB036S4M MPB048S4M
Number of Zones Up to 4 Up to 5
1
AHRI Ratings SystemType Ducted Non-Ducted Ducted Non-Ducted
Cooling-Btuh 36,000 36,000 48,000 48,000
HighTemperatureHeating-Btuh 36,000 36,000 50,000 48,000
LowTemperatureHeating-Btuh 22,800 24,600 33,000 29,600
SEER 17.9 22.5 17.6 22.4
EER 10.0 11.5 10.1 12.5
HSPF(RegionIV) 9.7 10.2 10.1 10.2
AHRIReferenceNumber 10062015 10062014 10062017 10062016
Energy Star No No No Yes
Ambient Temperature Range - °F Cooling –13 - 122 –13 - 122
Heating –13 - 86 –13 - 86
Sound Data (dBA) Cooling 62 64
Heating 62 64
Refrigerant Chargefurnished(R-410A) 6lbs.10oz. 10lbs.2oz.
Maximumlinelengthwithfurnishedcharge(perzone)-ft. 25 25
Additionalchargerequiredperft.-oz. 0.161 0.32
Compressor No.andType (1)Rotary (1)TwinRotary
Refrigerantoiltype VG74 VG74
Refrigerantoilcharge-oz. 33.8 47.3
Connections Liquid+Gas+Gaspipe(in.)are (4)1/4+(3)3/8+(1)1/2 (5)1/4+(3)3/8+(2)1/2
Max.lengthforallrooms-ft. 262 262
Max.lengthforoneindoorunit-ft. 115 115
Max.heightdifferencebetweenindoorandoutdoorunits-ft. 49 49
Max.heightdifferencebetweenindoorunits-ft. 33 33
Outdoor Fan (No.)Diameter-in. (1) 20 (2) 22
Totalairvolume-cfm 2130 4500
Motor rpm 150/200/250/300/400/500/600/750/
900/1000
150/200/250/300/400/500/600/700/
800/870
Outdoor Coil Numberofrows 2 2
Finsperinch 19 18
Fintype HydrophilicAluminum
Tubeoutsidediameter-in. 3/8 3/8
Tubetype RiedCopperTubing
Net face area - ft.
2
8.16 6.43(innercoil)/6.97(outercoil)
Application area - sq. ft. 515 - 755 690 - 1010
Design Pressure PSIG 550/340 550/340
Shipping Data Net/Shippingweight(lbs.) 157 / 168 224/255
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase 208/230V 208/230V
2
MaximumOvercurrentProtection(amps) 45 50
3
Minimum circuit ampacity 30 35
CompressorRatedloadamps 22 21
Outdoor Fan Motor Ratedloadamps 1.3 (2) 0.39
Output-W 120 (2) 85
NOTE-PerAHRI,thecertiedratingsforsystemsarevalidforallcombinationsofindoorunitswiththespecicoutdoorunitslistedaboveandintheAHRIDirectoryof
CertiedEquipment.Pleasevisithttp://www.ahridirectory.orgforfurtherdetailsandlatestupdates.
1
RatingsareAHRIcertiedtoAHRIStandard1230-2010withAddendum2;
•CoolingRatings-80°Fdrybulb/67°Fwetbulbenteringindoorcoilairand95°Fdrybulb/75°Fwetbulboutdoorairtemperature.
•HighTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand47°Fdrybulb/43°Fwetbulboutdoorairtemperature.
•LowTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand17°Fdrybulb/15°Fwetbulboutdoorairtemperature.
NOTE-Extremesofoperatingrangeareplusandminus10%oflinevoltage.
2
HACRtypecircuitbreakerorfuse.
3
RefertoNationalorCanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
NOTE-Adaptorsarefurnishedforthegaspipeconnections:
036 - (3) 3/8 x 1/2 in. and (1) 1/2 x 3/8 in.
048-(3)3/8x1/2in.,(2)1/2x3/8in.,(2)1/4x3/8in.and(2)1/2x5/8in.

Table of Contents

Other manuals for Lennox MCFA036S4-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCFA036S4-*P and is the answer not in the manual?

Lennox MCFA036S4-*P Specifications

General IconGeneral
BrandLennox
ModelMCFA036S4-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals