EasyManuals Logo
Home>Lennox>Air Conditioner>MCFA036S4-*P

Lennox MCFA036S4-*P User Manual

Lennox MCFA036S4-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
80
SUSPENSION RODS
DRAIN LINE
STRUCTURAL CEILING
8 in.
(203 mm)
Max. 28 in.
SUPPORT
STRAPS
3 ft. (1 m)
Figure 54. Condensate Drain with Pump
5. After system installation is complete, the condensate drain line must be checked for leaks and the condensate
pumps must be checked to ensure proper operation. This check is part of the start-up process which must be
done by the installing contractor. Turnthecondensatedrainpantestcoverlatchcounterclockwisetoopenthecover
andaccessthedrainpan. Seegurebelow.Funnelenoughwatertoengagethepumpintothe drainpanthrougha
exibletube.
6. Operatethesysteminthecoolingmode.Iftheinternalpumpisbeingused,ensurethatthepumpisoperatingandthe
waterinthepanisdrainingfreely.Iftheinternalpumpisnotbeingused,pourthewaterintothedrainpanandconrm
thatithasowedfreelyoutofthepanandoutofthedraintermination.Ifaleakisfound,shutdownpowertotheunitat
onceanddonotrestorepowertotheunituntiltheproblemhasbeenresolved.
7. Returnthetestcoverandturnthelatchclockwisetore-lockit.
DRAIN PAN
TEST COVER
FUNNEL WATER INTO
PAN THROUGH TUBE
FOR TEST
COVER LATCH
(Turn latch
counterclockwise
to unlock)
CL
OSE
D
O
PE
N
CLOS
E
D
O
PE
N
Figure 55. Condensate Drain Test
14.3.1.2 M22A, M33A and M33B
CAUTION
Makesurethatdrainpipingisproperlyroutedandinsulatedinordertopreventbothleaksandcondensation.
IMPORTANT
Drainshouldhaveaslopeofatleast¼inchperfootandshouldbeapprovedcorrosion-resistantpipe.Youmustconrm
operationofeverydrainandpumpinthesystemaspartofthecommissioningprocedure.
1. Useaeld-providedhoseclamptosecurethedrainlinestubonthesideofthecassettebasetoaeld-supplied1”(25
mm) drain line.
NOTE: Take care not to over-tighten the hose clamp as this may damage the drain line stub.
2. Seegurebelowforapplicationsusingtheunit’sinternalcondensatepumptoprovideliftintoadrain.Ensurethatthe
maindrainlineisproperlysloped(nolessthan1/4inchperfoot(18mmperm)).
3. Drainshouldbeasshortaspossibleandshouldnothaveanydroopsorkinksthatwouldrestrictcondensateowand
shallbeapprovedresistantpipe.

Table of Contents

Other manuals for Lennox MCFA036S4-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCFA036S4-*P and is the answer not in the manual?

Lennox MCFA036S4-*P Specifications

General IconGeneral
BrandLennox
ModelMCFA036S4-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals