Flame (microamp) signal is an electrical current which
passes from the integrated control to the sensor during
unit operation. Current passes from the sensor through
the ame to ground to complete a safety circuit.
To Measure Flame Signal - Integrated Control:
Use a digital readout meter capable of reading DC micro-
amps.
See gure 8 and table 6 for ame signal check.
1 - Set the meter to the DC amps scale.
2 - Turn o󰀨 supply voltage to control.
3 - Remove sensor wire from integrated control.
4 - Connect (-) lead to ame sensor wire.
5 - Connect (+) lead to Terminal FS on integrated control.
6 - Turn supply voltage on and close thermostat contacts
to cycle system.
7 - When main burners are in operation for two minutes,
take reading.
TABLE 6
Flame Signal in Microamps
Normal Low Drop Out
1.5 or greater 0.5 - 1.4 0.4 or less
Measuring Flame Signal
(Typical Furnace and Control)
Flame
Sensor
Flame Sensor
Wire
Integrated
Control
Remove Sensor Wire from
Integrated Control and
Connect Alligator Clip (−)
to Flame Sensor Lead
Flame Sensor
Terminal
Remove Sensor Wire from
Integrated Control and
Connect Alligator Clip (+)
to Terminal on Control
(+)
DIGITAL METER
(+) To Control
Sensor
Terminal
(-) To
flame
sensor
Set dial to measure dc microamps
(+)
Red Collar
Indicates
Positive
Lead
FIGURE 8

Other manuals for Lennox ML180UHE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ML180UHE Series and is the answer not in the manual?

Lennox ML180UHE Series Specifications

General IconGeneral
BrandLennox
ModelML180UHE Series
CategoryFurnace
LanguageEnglish

Related product manuals