V-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
NOTE- The following is a generalized procedure and does
not apply to all thermostat controls.
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat
subbase fan switch. With fan switch in ON position,
blower operates continuously. With fan switch in
AUTO position, blower cycles with demand or runs
continuously while heating or cooling circuit cycles.
3 - Depending on the type of indoor thermostat, blower
and entire unit will be o󰀨 when the system switch is
in OFF position.
B-Temperature Rise (Figure 23)
Temperature rise for ML180UHE(X) units depends on unit
input, blower speed, blower horsepower and static pres-
sure as marked on the unit rating plate. The blower speed
must be set for unit operation within the range of “TEMP.
RISE °F” listed on the unit rating plate.
°
TEMPERATURE RISE
Supply Duct Temperature ________
Return Duct Temperature
_
_____
Temperature Rise = ________
SUPPLY
AIR
Temperatures
RETURN AIR
FIGURE 23
C-External Static Pressure
1 - Tap locations shown in gure 24 .
2 - Punch a 1/4” diameter hole in supply and return
air plenums. Insert manometer hose ush with
inside edge of hole or insulation. Seal around the
hose with permagum. Connect the zero end of the
manometer to the discharge (supply) side of the
system. On ducted systems, connect the other end
of manometer to the return duct as above.
3 - With only the blower motor running and the
evaporator coil dry, observe the manometer
reading. Adjust blower motor speed to deliver the
air desired according to the job requirements. For
heating speed external static pressure drop must
not be more than 0.5” W.C. For cooling speed
external static pressure drop must not be more than
0.8” W.C.
4 - Seal the hole when the check is complete.
EXTERNAL STATIC PRESSURE
Supply Duct Static ________
Return Duct Static + _____
Total Duct Static = ________ (dry coil)
Duct Static
or
Supply Air
Return Air
FIGURE 24

Other manuals for Lennox ML180UHE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ML180UHE Series and is the answer not in the manual?

Lennox ML180UHE Series Specifications

General IconGeneral
BrandLennox
ModelML180UHE Series
CategoryFurnace
LanguageEnglish

Related product manuals