103
Error Code: E2
Description: Communicationmalfunctionbetweenoutdoorunitandallindoorunits.
General Note: Indoorunitdoesnotreceivethecommunicationfromoutdoorunitfor120secondsoroutdoorunitdoesnotreceivethe
communication from any one indoor unit for 180 seconds.
E2
Start:Poweroff,thenPowerontheoutdoorunitby
theBreaker.(reconnectthepowerwire).Isitstill
displayingtheerrorcode?
Checkwiringontheoutdoorandindoor
terminalsfollowthewiringdiagram.Areall
oftheconnectionscorrect?
Yes
Yes
Correctthewiring
No
Turnonallindoorunitsbytheremote
controller. Are all indoor units displaying
correctly?
No
Measure Vs, is it moving alternately
betweenpositivevalueandnegative
value?(Vsisthevoltagebetween3
and2).ReferPic1
No
A:Isallthewiringbetween
terminalsandindoorPCB
connectedcorrectly`?
No
No
Reconnectthewiring
Yes
ChangetheIndoorPCB
Yes
Poweronbyremotecontroller,itis
stilldisplayingtheerrorcodeafter
3minutes?
No
Yes
Turnoffalloftheindoorunits.Is
IPMpowerLEDoperatingLED
lampon?RefertoPic2.
Yes
Yes
ChangeIPM
No
Yes
Ismainboard”88”lampon?
ReferPic3.
No
Isthereactor
wiringproperly
connected?
No
Reconnectthe
wiring
Yes
ChangeOutdoorMainPCB
Yes
Aretheindoorunitsnumberedcorrectly?Check
ontheoutdoorcheckpoint.(2for2-zone,3for
3-zone,4for4-zone,5for5-zone).ReferPIC4.
Problem Solved
ChangeoutdoorunitPCBas-
semblytotally(includewiring).
Norsttime
No second time
A