88
When the electronic scale displays the proper weight
(refer to the table), disconnect the charge hose from
the 3-way valve’s service port immediately and turn
off the air conditioner before disconnecting the hose.
Mount the valve stem caps and the service port Use
a torque wrench to tighten the service port cap to a
torque of 18N.m (13.27 ft·lbs).
Be sure to check for gas leaks.
18.2.6. Add Refrigerant after Long-Term
System Operation
Connect the charge hose to the 3-way service port
and open the 2-way and 3-way valve.
Connect the charge hose to the valve at the bottom
of the cylinder. If the refrigerant is R410A, place the
cylinder bottom-up to ensure liquid charge.
Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
Place the charging cylinder onto the electronic scale
and record the weight.
Turn on the air conditioner in cooling mode.
Open the valves (Low side)on the charge set and
charge the system with liquid refrigerant.
When the electronic scale displays the proper weight
(refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3- way
valve’s service port immediately and turn off the air
conditioner before disconnecting the hose.
Mount the valve stem caps and the service port. Use
torque wrench to tighten the service port cap to a
torque of 18N.m(13.27 ft·lbs).
Be sure to check for gas leaks.
18.2.7. Servicing Indoor Unit Refrigeration
Circuit
18.2.7.1 Collecting Refrigerant into Outdoor
Unit
Conrm that both the 2-way and 3-way valves are
set to the opened position
Remove the valve stem caps and conrm that the
valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the
valve stems.
Connect the charge hose with the push pin of handle
lo to the 3-way valves gas service port.
Air purging of the charge hose - Open the handle
Lo valve of the manifold valve slightly to purge air
from the charge hose for 5 seconds and then close it
quickly.
Set the 2-way valve to the close position. 5). Operate
the air conditioner at the cooling cycle and stop it
when the gauge indicates 0.1MPa (14 psi).
Set the 3-way valve to the closed position
immediately
Do this quickly so that the gauge ends up indicating
0.3 to 0.5Mpa (43 - 72 psi).
Disconnect the charge set, and tighten the 2-way
and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves
service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
18.2.7.2 Air Purging with Vacuum Pump
Completely tighten the are nuts of the indoor and
outdoor units, conrm that both the 2-way and 3-way
valves are set to the closed position.
Connect the charge hose with the push pin of handle
lo to the 3-way valves gas service port.
Connect the charge hose of handle hi connection to
the vacuum pump.
Fully open the handle Lo of the manifold valve.
Operate the vacuum pump to evacuate.
Make evacuation for 30 minutes and check whether
the compound meter indicates - 0.1Mpa (500
microns). If the meter does not indicate - 0.1Mpa
(500 microbars) after pumping 30 minutes, it should
be pumped 20 minutes more. If the pressure can’t
achieve -0.1Mpa (500 microbars) after pumping 50
minutes, please check if there are some leakage
points.
Fully close the handle Lo valve of the manifold valve
and stop the operation of the vacuum pump. Conrm
that the gauge needle does not move (approximately
5 minutes after turning off the vacuum pump).
Turn the are nut of the 3-way valves about 45°
counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the are nut again. Make
sure the pressure display in the pressure indicator
is a little higher than the atmosphere pressure. Then
remove the charge hose from the 3 way valve.
Fully open the 2 way valve and 3 way valve and
securely tighten the cap of the 3 way.

Table of Contents

Other manuals for Lennox MMDB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MMDB and is the answer not in the manual?

Lennox MMDB Specifications

General IconGeneral
BrandLennox
ModelMMDB
CategoryAir Conditioner
LanguageEnglish

Related product manuals