NOTES: For Temperatures and Capacities not shown in tables, see bulletin ā Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS 10 TON
TS 6 to 20 Ton Rā410A Air Conditioners / Page 21
DOWNāFLOW INDOOR COILS
COOLING CAPACITY ā TSA120S4S with [(2) CR33ā50/60Cā2F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
3200 1510 107.9 31.6 7.00 .71 .84 .98 103.4 30.3 7.81 .72 .86 .99 98.5 28.9 8.74 .73 .89 1.00 93.1 27.3 9.79 .75 .91 1.00
4000 1890 112.7 33.0 7.08 .75 .91 1.00 107.7 31.6 7.89 .77 .94 1.00 102.4 30.0 8.81 .79 .96 1.00 96.7 28.3 9.85 .81 .98 1.00
4800 2265 115.9 34.0 7.13 .80 .97 1.00 111.0 32.5 7.94 .82 .99 1.00 106.1 31.1 8.87 .84 1.00 1.00 100.7 29.5 9.92 .87 1.00 1.00
67_F
(19_C)
3200 1510 114.0 33.4 7.11 .57 .69 .81 109.1 32.0 7.92 .57 .70 .83 103.9 30.5 8.83 .58 .71 .85 98.4 28.8 9.88 .59 .73 .88
4000 1890 118.8 34.8 7.19 .59 .73 .88 113.7 33.3 7.99 .60 .74 .90 108.1 31.7 8.90 .61 .76 .93 102.1 29.9 9.94 .63 .79 .96
4800 2265 122.4 35.9 7.25 .62 .78 .95 117.0 34.3 8.06 .63 .79 .97 111.0 32.5 8.96 .64 .82 .99 104.7 30.7 9.99 .66 .85 1.00
71_F
(22_C)
3200 1510 119.6 35.1 7.20 .43 .55 .67 114.7 33.6 8.01 .43 .56 .68 109.2 32.0 8.93 .44 .57 .69 103.5 30.3 9.97 .44 .58 .71
4000 1890 124.6 36.5 7.30 .44 .58 .71 119.5 35.0 8.10 .45 .59 .72 113.7 33.3 9.01 .45 .60 .74 107.3 31.4 10.04 .45 .62 .77
4800 2265 128.5 37.7 7.37 .45 .61 .75 122.9 36.0 8.17 .46 .62 .77 116.8 34.2 9.07 .46 .63 .80 110.2 32.3 10.10 .47 .65 .82
HORIZONTAL INDOOR COILS
COOLING CAPACITY ā TSA120S4S with [(2) CH33ā62Dā2F]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
3200 1510 109.7 32.1 7.03 .70 .83 .96 105.1 30.8 7.84 .71 .84 .98 100.3 29.4 8.77 .72 .86 1.00 95.0 27.8 9.81 .74 .89 1.00
4000 1890 114.9 33.7 7.12 .74 .89 1.00 110.1 32.3 7.93 .75 .91 1.00 104.8 30.7 8.85 .77 .94 1.00 99.0 29.0 9.89 .79 .97 1.00
4800 2265 118.8 34.8 7.19 .78 .95 1.00 113.5 33.3 8.00 .79 .98 1.00 108.0 31.7 8.90 .82 1.00 1.00 102.1 29.9 9.94 .84 1.00 1.00
67_F
(19_C)
3200 1510 115.2 33.8 7.13 .56 .67 .79 110.5 32.4 7.94 .56 .68 .81 105.3 30.9 8.86 .57 .70 .83 100.0 29.3 9.91 .58 .71 .85
4000 1890 121.0 35.5 7.23 .58 .71 .85 115.7 33.9 8.03 .59 .73 .87 110.2 32.3 8.94 .60 .74 .90 104.1 30.5 9.98 .61 .77 .94
4800 2265 124.8 36.6 7.30 .60 .75 .92 119.4 35.0 8.11 .61 .77 .94 113.8 33.4 9.01 .63 .79 .97 107.2 31.4 10.03 .64 .82 1.00
71_F
(22_C)
3200 1510 121.3 35.5 7.24 .43 .54 .65 116.4 34.1 8.04 .43 .55 .66 111.1 32.6 8.96 .44 .56 .67 105.3 30.9 10.00 .44 .57 .69
4000 1890 126.9 37.2 7.34 .44 .57 .69 121.8 35.7 8.14 .44 .58 .71 115.9 34.0 9.06 .45 .59 .72 109.5 32.1 10.08 .45 .60 .75
4800 2265 131.2 38.5 7.43 .45 .59 .73 125.5 36.8 8.22 .45 .60 .75 119.4 35.0 9.12 .46 .62 .77 112.5 33.0 10.14 .47 .63 .80