NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS 20 TON (DUAL CIRCUIT)
TS 6 to 20 Ton R−410A Air Conditioners / Page 28
AIR HANDLERS
COOLING CAPACITY − TSA240S4D (FIRST STAGE) with [TAA240S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
6400 3020 124.8 36.6 5.92 .72 .84 .95 120.3 35.3 6.61 .73 .85 .97 115.7 33.9 7.37 .74 .87 .98 110.8 32.5 8.25 .75 .89 1.00
8000 3775 130.7 38.3 6.02 .76 .90 1.00 125.9 36.9 6.70 .77 .92 1.00 121.0 35.5 7.46 .79 .93 1.00 115.6 33.9 8.33 .80 .96 1.00
9600 4530 135.1 39.6 6.09 .81 .96 1.00 129.9 38.1 6.75 .82 .97 1.00 124.9 36.6 7.52 .84 .99 1.00 119.4 35.0 8.39 .86 1.00 1.00
67_F
(19_C)
6400 3020 132.3 38.8 6.03 .57 .70 .81 127.4 37.3 6.72 .58 .70 .82 122.6 35.9 7.48 .59 .72 .84 117.3 34.4 8.36 .59 .73 .85
8000 3775 138.2 40.5 6.14 .60 .74 .87 133.1 39.0 6.81 .61 .75 .88 128.1 37.5 7.58 .61 .77 .90 122.4 35.9 8.44 .62 .79 .93
9600 4530 142.9 41.9 6.22 .63 .79 .93 137.6 40.3 6.89 .63 .80 .95 132.0 38.7 7.64 .65 .82 .96 125.9 36.9 8.50 .66 .84 .98
71_F
(22_C)
6400 3020 139.3 40.8 6.16 .44 .56 .67 134.2 39.3 6.83 .45 .56 .68 129.0 37.8 7.59 .45 .57 .69 123.4 36.2 8.46 .45 .58 .70
8000 3775 145.4 42.6 6.26 .45 .58 .72 140.2 41.1 6.93 .46 .59 .73 134.7 39.5 7.69 .46 .60 .74 129.0 37.8 8.56 .46 .62 .76
9600 4530 150.2 44.0 6.34 .46 .61 .76 144.5 42.3 7.01 .46 .62 .78 138.6 40.6 7.75 .46 .63 .80 132.4 38.8 8.62 .47 .65 .81
COOLING CAPACITY − TSA240S4D (SECOND STAGE) with [TAA240S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
6400 3020 231.4 67.8 14.74 .74 .87 .98 221.6 64.9 16.50 .75 .89 1.00 210.8 61.8 18.52 .77 .91 1.00 199.1 58.4 20.85 .79 .93 1.00
8000 3775 242.0 70.9 14.91 .79 .93 1.00 231.2 67.8 16.66 .80 .96 1.00 219.2 64.2 18.66 .83 .98 1.00 207.4 60.8 20.98 .85 1.00 1.00
9600 4530 249.8 73.2 15.05 .84 .99 1.00 238.9 70.0 16.79 .86 1.00 1.00 227.5 66.7 18.81 .88 1.00 1.00 215.8 63.2 21.09 .90 1.00 1.00
67_F
(19_C)
6400 3020 245.2 71.9 14.95 .59 .72 .84 234.6 68.8 16.71 .59 .73 .85 223.2 65.4 18.72 .60 .74 .87 211.1 61.9 21.04 .62 .76 .90
8000 3775 256.1 75.1 15.16 .61 .77 .90 244.8 71.7 16.87 .62 .79 .93 232.1 68.0 18.86 .64 .80 .95 219.1 64.2 21.14 .65 .83 .98
9600 4530 263.9 77.3 15.29 .65 .82 .96 251.7 73.8 16.99 .66 .84 .98 238.8 70.0 18.97 .67 .86 1.00 224.0 65.6 21.22 .69 .88 1.00
71_F
(22_C)
6400 3020 257.9 75.6 15.18 .45 .57 .69 246.9 72.4 16.92 .45 .58 .70 235.2 68.9 18.91 .45 .59 .72 222.3 65.1 21.22 .46 .60 .74
8000 3775 269.4 79.0 15.38 .46 .60 .74 258.0 75.6 17.12 .46 .62 .76 244.8 71.7 19.10 .46 .63 .78 231.0 67.7 21.37 .47 .65 .80
9600 4530 277.1 81.2 15.51 .46 .63 .80 264.8 77.6 17.23 .47 .65 .81 251.1 73.6 19.20 .47 .66 .84 236.8 69.4 21.47 .48 .68 .86
COOLING CAPACITY − TSA240S4D (FIRST STAGE) with [(2) TAA120S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
6400 3020 127.0 37.2 5.95 .72 .84 .96 122.5 35.9 6.64 .73 .86 .97 117.7 34.5 7.42 .74 .87 .99 112.5 33.0 8.29 .76 .89 1.00
8000 3775 133.4 39.1 6.06 .77 .90 1.00 128.4 37.6 6.73 .78 .92 1.00 123.4 36.2 7.50 .79 .94 1.00 117.9 34.6 8.37 .81 .96 1.00
9600 4530 138.4 40.6 6.14 .81 .96 1.00 133.1 39.0 6.81 .83 .98 1.00 127.6 37.4 7.57 .84 .99 1.00 121.7 35.7 8.43 .86 1.00 1.00
67_F
(19_C)
6400 3020 134.6 39.4 6.08 .58 .69 .81 129.8 38.0 6.76 .58 .71 .82 124.6 36.5 7.52 .59 .71 .84 119.4 35.0 8.38 .59 .73 .86
8000 3775 141.3 41.4 6.19 .60 .75 .87 135.9 39.8 6.86 .61 .76 .89 130.2 38.2 7.61 .61 .77 .91 124.5 36.5 8.47 .63 .79 .93
9600 4530 145.8 42.7 6.26 .63 .79 .93 140.2 41.1 6.93 .64 .81 .95 134.1 39.3 7.68 .65 .82 .97 128.0 37.5 8.53 .66 .84 .99
71_F
(22_C)
6400 3020 142.7 41.8 6.22 .44 .56 .67 137.4 40.3 6.89 .44 .57 .68 131.9 38.7 7.64 .44 .57 .69 126.2 37.0 8.51 .45 .58 .71
8000 3775 148.7 43.6 6.31 .45 .58 .72 143.6 42.1 7.00 .46 .60 .73 137.5 40.3 7.74 .46 .61 .74 131.2 38.5 8.60 .46 .61 .76
9600 4530 153.4 45.0 6.40 .46 .61 .76 147.6 43.3 7.07 .46 .63 .78 141.5 41.5 7.81 .47 .64 .80 134.9 39.5 8.66 .47 .65 .82
COOLING CAPACITY − TSA240S4D (SECOND STAGE) with [(2) TAA120S4D]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
6400 3020 235.4 69.0 14.83 .74 .87 .99 225.0 65.9 16.58 .76 .89 1.00 214.1 62.7 18.55 .77 .91 1.00 202.4 59.3 20.87 .79 .94 1.00
8000 3775 246.8 72.3 15.00 .79 .94 1.00 235.8 69.1 16.73 .81 .96 1.00 224.1 65.7 18.76 .83 .98 1.00 210.9 61.8 21.01 .85 1.00 1.00
9600 4530 255.3 74.8 15.14 .84 .99 1.00 243.5 71.4 16.86 .86 1.00 1.00 233.4 68.4 18.89 .88 1.00 1.00 220.9 64.7 21.21 .91 1.00 1.00
67_F
(19_C)
6400 3020 249.1 73.0 15.04 .59 .71 .84 238.9 70.0 16.77 .59 .73 .86 227.4 66.6 18.80 .61 .75 .88 214.2 62.8 21.06 .62 .77 .90
8000 3775 260.4 76.3 15.21 .61 .77 .91 249.0 73.0 16.95 .63 .79 .93 236.1 69.2 18.92 .64 .81 .95 221.7 65.0 21.17 .65 .83 .98
9600 4530 268.2 78.6 15.35 .65 .82 .97 256.1 75.1 17.06 .66 .84 .99 243.2 71.3 19.05 .67 .86 1.00 228.2 66.9 21.28 .69 .89 1.00
71_F
(22_C)
6400 3020 263.8 77.3 15.28 .44 .57 .69 252.4 74.0 17.01 .45 .58 .71 240.3 70.4 18.99 .46 .59 .72 226.7 66.4 21.28 .46 .60 .74
8000 3775 275.0 80.6 15.48 .46 .61 .74 262.4 76.9 17.20 .46 .61 .76 249.6 73.2 19.16 .47 .63 .79 235.0 68.9 21.44 .47 .65 .81
9600 4530 283.0 82.9 15.62 .47 .64 .80 269.7 79.0 17.32 .47 .65 .82 255.7 74.9 19.31 .49 .67 .84 240.2 70.4 21.55 .48 .68 .87