NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
RATINGS 6 TON
TS 6 to 20 Ton R−410A Air Conditioners / Page 16
AIR HANDLERS
COOLING CAPACITY − TSA072S4S with [CBX27UH−060]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
1920 905 69.1 20.3 4.83 .68 .83 .98 66.2 19.4 5.37 .70 .86 1.00 62.8 18.4 5.97 .71 .89 1.00 59.1 17.3 6.66 .74 .93 1.00
2400 1135 72.6 21.3 4.86 .73 .91 1.00 69.5 20.4 5.40 .75 .94 1.00 66.2 19.4 6.00 .77 .97 1.00 62.4 18.3 6.69 .80 1.00 1.00
2880 1360 75.7 22.2 4.87 .78 .97 1.00 72.6 21.3 5.42 .80 1.00 1.00 68.9 20.2 6.01 .84 1.00 1.00 65.3 19.1 6.71 .88 1.00 1.00
67_F
(19_C)
1920 905 72.7 21.3 4.86 .55 .66 .79 69.7 20.4 5.39 .55 .67 .81 66.1 19.4 5.99 .56 .69 .84 62.3 18.3 6.69 .57 .71 .88
2400 1135 76.3 22.4 4.88 .57 .70 .87 72.9 21.4 5.41 .58 .72 .90 69.2 20.3 6.03 .59 .75 .93 65.0 19.0 6.71 .61 .78 .97
2880 1360 79.0 23.2 4.90 .60 .75 .94 75.4 22.1 5.43 .61 .78 .97 71.5 21.0 6.04 .62 .81 1.00 67.2 19.7 6.74 .64 .85 1.00
71_F
(22_C)
1920 905 76.3 22.4 4.88 .41 .53 .64 73.0 21.4 5.42 .42 .54 .65 69.5 20.4 6.02 .42 .55 .67 65.4 19.2 6.71 .42 .56 .69
2400 1135 80.0 23.4 4.90 .42 .56 .68 76.4 22.4 5.44 .43 .57 .70 72.7 21.3 6.05 .44 .58 .72 68.3 20.0 6.74 .44 .60 .75
2880 1360 82.7 24.2 4.91 .44 .59 .73 79.1 23.2 5.46 .44 .60 .75 75.0 22.0 6.07 .45 .61 .78 70.5 20.7 6.77 .46 .63 .82
COOLING CAPACITY − TSA072S4S with [CBX32M−060]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
1920 905 69.2 20.3 4.84 .68 .82 .97 66.0 19.3 5.37 .69 .85 .99 62.5 18.3 5.97 .70 .87 1.00 58.7 17.2 6.65 .72 .91 1.00
2400 1135 72.5 21.2 4.85 .72 .90 1.00 69.1 20.3 5.40 .74 .93 1.00 65.5 19.2 6.00 .76 .96 1.00 61.5 18.0 6.68 .79 .98 1.00
2880 1360 75.0 22.0 4.87 .77 .96 1.00 71.6 21.0 5.41 .79 .98 1.00 67.8 19.9 6.01 .82 1.00 1.00 63.8 18.7 6.70 .85 1.00 1.00
67_F
(19_C)
1920 905 73.0 21.4 4.86 .54 .65 .78 69.7 20.4 5.40 .55 .67 .80 66.0 19.3 6.00 .55 .68 .83 61.9 18.1 6.69 .56 .70 .87
2400 1135 76.2 22.3 4.88 .56 .69 .86 72.6 21.3 5.41 .57 .71 .88 68.9 20.2 6.02 .58 .73 .92 64.7 19.0 6.70 .60 .76 .95
2880 1360 78.8 23.1 4.90 .59 .74 .93 75.2 22.0 5.43 .60 .76 .95 71.2 20.9 6.04 .61 .79 .98 66.7 19.5 6.73 .62 .82 1.00
71_F
(22_C)
1920 905 76.8 22.5 4.88 .41 .52 .63 73.5 21.5 5.42 .42 .53 .64 69.7 20.4 6.03 .42 .54 .66 65.5 19.2 6.71 .42 .55 .68
2400 1135 80.3 23.5 4.91 .42 .55 .67 76.7 22.5 5.44 .43 .56 .69 72.7 21.3 6.05 .43 .57 .70 68.2 20.0 6.74 .44 .58 .73
2880 1360 82.8 24.3 4.92 .43 .57 .71 78.9 23.1 5.46 .44 .59 .73 74.8 21.9 6.07 .44 .60 .76 70.1 20.5 6.76 .45 .62 .79
COOLING CAPACITY − TSA072S4S with [TAA072S4S]
Entering
Wet Bulb
Tempera-
ture
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cooling
Capacity
Comp
Motor
kW
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
cfm L/s kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
kBtuh kW
75_F
24_C
80_F
27_C
85_F
29_C
63_F
(17_C)
1920 905 70.4 20.6 4.84 .68 .83 .99 67.2 19.7 5.38 .69 .86 1.00 63.7 18.7 5.98 .71 .89 1.00 59.7 17.5 6.67 .73 .93 1.00
2400 1135 74.0 21.7 4.87 .73 .92 1.00 70.5 20.7 5.40 .75 .95 1.00 66.9 19.6 6.01 .77 .98 1.00 62.6 18.3 6.69 .80 1.00 1.00
2880 1360 76.7 22.5 4.88 .78 .99 1.00 72.9 21.4 5.41 .80 1.00 1.00 69.4 20.3 6.02 .84 1.00 1.00 65.7 19.3 6.72 .87 1.00 1.00
67_F
(19_C)
1920 905 74.2 21.7 4.86 .54 .66 .79 70.9 20.8 5.41 .55 .67 .81 67.0 19.6 6.01 .56 .69 .84 63.1 18.5 6.70 .57 .71 .88
2400 1135 77.7 22.8 4.89 .57 .70 .87 74.1 21.7 5.43 .58 .72 .90 70.3 20.6 6.03 .59 .74 .94 65.9 19.3 6.72 .60 .77 .98
2880 1360 80.4 23.6 4.90 .59 .75 .95 76.7 22.5 5.45 .61 .78 .98 72.5 21.2 6.05 .62 .81 1.00 68.0 19.9 6.74 .63 .84 1.00
71_F
(22_C)
1920 905 78.4 23.0 4.89 .41 .53 .64 74.9 22.0 5.43 .41 .53 .65 71.1 20.8 6.04 .42 .55 .66 66.6 19.5 6.72 .42 .55 .68
2400 1135 81.9 24.0 4.92 .42 .56 .68 78.1 22.9 5.45 .43 .56 .70 73.9 21.7 6.06 .43 .58 .72 69.4 20.3 6.75 .44 .59 .74
2880 1360 84.3 24.7 4.93 .43 .58 .73 80.4 23.6 5.47 .44 .59 .75 76.1 22.3 6.08 .45 .61 .78 71.4 20.9 6.77 .45 .62 .81