blocked or dirty coil. The low pressure switch (SPST,
NO) protects the systemcompressor from damagedue
to loss of charge. The switch will trip at 15 +/-- 5 psig
(103 +/-- 34 kPa) and automatically resets at 25 +/--3 psig
(172 +/-- 21 kPa).
Refrigerant Sight Glass (Option Units ONLY)
A refrigerant sight glass is provided in the bag assem-
bly for field installation. Thesight glass can beinstalled
in the liquid line to help monitor system charge.
0$,17(1$1&(
:$51,1*
(OHFWULF VKRFN KD
]DUG &DQ FDXVH LQMX
U\ RU GHDWK %HIRUH DWWHPSWLQJ WR SHU
IRUP DQ\ VHUYLFH RU PDLQWHQDQFH WXUQ
WKH HOHFWULFDO SRZHU WR XQLW 2)) DW GLV
FRQQHFW VZLWFKHV 8QLW PD\ KDYH
PXOWLSOH SRZHU VXSSOLHV
At the beginning of each cooling season, the system
should be checked as follows:
1-- Clean and inspect condenser coil. Coil may be
flushed with a water hose. Make sure power is off
before cleaning.
2-- Visually inspect connecting lines and coils for evi-
dence of oil leaks.
3-- Check wiring for loose connections.
4-- Check for correct voltage at unit (unit operating).
5-- Check condenser fan motor amp--draw.
Unit nameplate _________ Actual ____________ .
127(,IRZQHU FRPSODLQV RI LQVXIILFLHQW FRROLQJ WKH
XQLW VKRXOG EH JDXJHG DQG UHIULJHUDQW FKDUJH
FKHFNHG 5HIHU WR VHFWLRQ RQ UHIULJHUDQW FKDUJLQJ LQ
WKLV LQVWUXFWLRQ
Evaporator Coil
1-- Clean coil, if necessary.
2-- Check connecting lines and coils for evidence of oil
leaks.
3-- Check condensate line and clean, if necessary.
Indoor Unit
1-- Clean or change filters.
2-- Adjust blower speed for cooling. The pressure drop
over the coil should be measured to determine the
correct blower CFM. Refer to the unit information
service manual for pressure drop tables and proce-
dure.
3--
Belt Drive Blowers --
Check belt for wear andproper
tension.
4-- Check all wiring for loose connections
5-- Check for correct voltage at unit (blower operat-
ing).
6-- Check amp-draw on blower motor
Unit nameplate_________ Actual ____________.
All manuals and user guides at all-guides.com
all-guides.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Value 10ACB Series and is the answer not in the manual?

Lennox Value 10ACB Series Specifications

General IconGeneral
BrandLennox
ModelValue 10ACB Series
CategoryHeat Pump
LanguageEnglish

Related product manuals