EasyManuals Logo
Home>Lennox>Heat Pump>VPB H4-3P Series

Lennox VPB H4-3P Series User Manual

Lennox VPB H4-3P Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
4
Installation Clearances - inches (mm)
12 (305) Minimum
(Wall or Partition)
Air Outlet
Air Inlet
Air inlet
Single Unit Installation
Parallel Units Side by Side
Parallel Units Back to Back, Facing and Front to Back
Front of Unit
Front of Units
12
(305)
Minimum
79 (2007)
Minimum
24
(610)
Minimum
(Service
Clearance)
12 (305) Minimum
79 (2007)
Minimum
24
(610)
Minimum
(Service Clearance)
12
(305)
Min.
118
(2997)
Min.
118
(2997)
Min.
20
(508)
Min.
79
(2007)
Min.
Back to Back Facing Units Front to Back
(Wall or Partition)
(Wall or Partition)
(Wall or Partition)
NOTE - 24 in. (610 mm) clearance required on top of unit.
NOTE - If unit is surrounded on three
or four sides by walls or partitions
that are taller than 10 ft. (3 m), call
Lennox VRF Applications group to
discuss additional requirements.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox VPB H4-3P Series and is the answer not in the manual?

Lennox VPB H4-3P Series Specifications

General IconGeneral
BrandLennox
ModelVPB H4-3P Series
CategoryHeat Pump
LanguageEnglish

Related product manuals