Commissioning
5-2 UOMu_^MVMO
5.2 Short set-up (Factory setting)
5.2.1 Switch-on sequence
Step
1.Switch on mains voltage
2.Select the direction of rotation. D CW rotation:
- Apply a LOW signal to terminal E4 (0...+3V).
D CCW rotation:
- Apply a HIGH s i gnal to terminal E4 (+12...+30V).
3.Select the s etpoint. Apply a voltage 0...+10 V to terminal 8.
4.Enable the controller. Apply a HIGH signal (+12...+30V) to terminal 28.
5.The drive is now operating according to factory
setting.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com