EasyManuals Logo
Home>Lenze>Control Unit>E82ZAFSC001

Lenze E82ZAFSC001 User Manual

Lenze E82ZAFSC001
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
Technical data
Connection data
4
EDK82ZAFSC DE/EN/FR 5.0
33
H1_Daten−Einsatzbed_Klima_FIF
4 Technical data
Connection data
X3/ Values
62 Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0  +60°C)
Carrying capacity I
max
= 2 mA
8
Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0  +60 °C)
Input resistance
l R
Input
> 50 kW (with voltage signal)
l R
Input
= 250 W (with current signal)
9 Carrying capacity I
max
= 10 mA
7 isolated from terminal X3/39 (GND2)
20
Load capacity: S I
max
= 40 mA
28
Input resistance: 3.3 kW
1 = HIGH (+12  +30 V), PLC level, HTL
0 = LOW (0  +3 V), PLC level, HTL
E1
1)
E2
1)
E3
E4
39 isolated from terminal X3/7 (GND1)
A1 Load capacity:
I
max
= 10 mA, with internal supply
I
max
= 50 mA, with external supply
1)
Frequency input alternatively 0  10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425
Operating conditions
Ambient conditions
Climate
Storage IEC/EN 60721−3−1 1K3 (−25 to +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 to +70 °C)
Operation Corresponding to the data of the Lenze basic device used (see
documentation of the basic device).
Pollution EN 61800−5−1 Degree of pollution 2