Installation
820XBA1097 4-11
Te rm i n a l Use
(Factory setting is printed in bold)
Level Data
Analog
7 GND 1
inputs
8 Setpoint input,
reference:
Te r min a l 7
(0 to 10V)
6
4
2
1
5-6
5-6
3-4
1-2
0to20mA
4to20mA
0to5V
0to10V
Resol ut ion: 9 bit
Linearity fault:
îš™
0.5 %
Temperature fault: 0.3 % (0...+40

C)
Input resistance
Current signal: 250

9 Supply for setpoint potentiometer 5.2V/ 6mA
Analog
output
62 Analog output, reference: terminal 7
(Field frequency)
0... 6 V/ 2
mA
Resol ut ion: 8 bit
Digital
inputs
20 Voltage supply for digital inputs
12 V/20 mA
28 Controller enable HIGH
HIGH:12V...30V
E4 CW rotation/
CCW rotation (CW/CCW)
CW: LOW
CCW: HIGH
LOW: 0 V ... 3 V
E3 DC-injection brake HIGH
E2
JOG frequencies
39 GND 2 (reference for external voltages)
Te rm i n a l Use
(Factory setting is printed in bold)
Relay position
(switched)
Data
Rel ay
output
K11 Relay output normally-closed contact
(TRIP)
opened
24 VAC/ 3,0 Aor
60 VDC/ 0.5 A
K1
K22 Relay mid-position contact
K24 Relay output normally-open contact
(TRIP)
closed