Troubleshooting and fault elimination
8-4 820XBA1097
Display RemedyCauseFault
OH Heatsinktemperatureis
higherthanthevalueset
inthecontroller
Ambienttemperature
T
amb
>+40

Cor+50

C
-
Allowcontrollertocoolandensure
ventilation
-
Checktheambienttemperaturein
thecontrolcabinet
Heatsinkverydirty Cleanheatsink
Incorrectmountingposition Changemountingposition
OH3 PTCmonitoring
Motortoohotbecauseof
excessivecurrentorfrequentand
toolongacceleration
Checkdrivedimensioning
PTCnotconnected ConnectPTCorswitchoffmonitoring
(C0585=3)
OH4 Overtemperatureunit Insideunittoohot
-
Reducecontrollerload
-
Improvecooling
-
Checkfaninthecontroller
OU Overvoltage
Mainsvoltagetoohigh Checkvoltagesupply
OU Overvoltage
Feedbackoperation
Brakingoperation
-
Increasedecelerationtimes.
-
Foroperationwithbrakechoppers:
-Checktheselectionand
connectionofthebrakeresistor
-Increasethedecelerationtimes
Earthleakageonthemotorside Checkmotorcableandmotorforearth
fault(disconnectmotorfrominverter)
OUE Overvoltage Mainsovervoltagelongerthan5s Checkmainsvoltage
rSt Faultyauto-TRIPreset Morethan8faultmessagesin
10minutes
Dependsonthefaultmessage
Pr Faultyparametertransfer
viatheoperatingmodule
PAR1andPAR2aredefective.
Itisabsolutelynecessarytorepeatthe
datatransferorloadthefactory
settingbeforeenablingthecontroller.
Pr1 FaultyPAR1transfervia
theoperatingmodule
PAR1isdefective.
datatransferorloadthefactory
settingbeforeenablingthecontroller.
Pr2 FaultyPAR2transfervia
theoperatingmodule
PAR2isdefective.