Electrical installation
EMC−compliant wiring
6
EDK82ZAFPC−001 DE/EN/FR 7.0
49
H1_E_INST−VorgehenVerdraht
6 Electrical installation
EMC−compliant wiring
For wiring according to EMC requirements observe the following points:
Note!
ƒ Separate control cables/data lines from motor cables.
ƒ Connect the shields of control cables/data lines at both ends in the case of
digital signals.
ƒ Use an equalizing conductor with a cross−section of at least 16mm
2
(reference:PE) to avoid potential differences between the bus nodes.
ƒ Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.
Wiring procedure
1. Observe the bus topology, do not use any stubs.
2. Observe the notes and wiring instructions given in the documents for the control
system.
3. Only use cables corresponding to the listed specifications (52).
4. Observe the notes for the voltage supply of the module (54).
5. Activate the bus terminating resistors on the first and last physical bus device (64).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze PROFIBUS E82ZAFPC001 and is the answer not in the manual?

Lenze PROFIBUS E82ZAFPC001 Specifications

General IconGeneral
BrandLenze
ModelPROFIBUS E82ZAFPC001
CategoryControl Unit
LanguageEnglish

Related product manuals