3.2 Electrical installation
3.2.1 Installation according to EMC requirements
EMC
Compliance with EN 61800-3/A11
Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint lter and the motor cable length does not
exceed 10m
A
Screen clamps
B
Control cable
C
Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D
Electrically conductive mounting plate
E
Filter (if required)
3.2.2 Fuses/cable cross-sections
Type
Installation to EN 60204-1 Installation to UL E.l.c.b.
(2)
Fuse Miniature
circuit
breaker
L1, L2/N,
L3, PE
Fuse
(3)
L1, L2/N,
L3, PE
[A] [A] [mm²] [A] [AWG]
ESMD251W2SFA … ESMD551W2SFA
ESMD371W2TXA … ESMD112W2TXA
10 C10 2.5 10 14
> 30 mA
ESMD152W2TXA 16 C16 2.5 12 14
ESMD751W2SFA, ESMD222W2TXA 16 C16 2.5 15 14
ESMD152W2SFA, ESMD302W2TXA 20 C20 4 20 12
ESMD222W2SFA, ESMD402W2TXA 25 C25 6
(4)
25 10
(1) Observe the applicable local regulations
(2) Pulse-current or universal-current sensitive earth leakage circuit breaker
(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R,
JJN, JJS or equivalent
(4) Connection without end ferrules or with attached pin end connectors
Observe the following when using E.l.c.b:
• Installation of E.l.c.b only between supplying mains and controller.
• The E.l.c.b can be activated by:
− capacitive leakage currents between the cable screens during operation (especially with
long, screened motor cables).
− connecting several controllers to the mains at the same time.
− RFI lters