Installation Manual 15
Installation Space
Installation Space
Individual Installation
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Category
Case 1
(10mm≤Side Space≤49mm)
Case 2
(Side Space
≥
49mm)
Installation Space
4 sides are
walls
Only 2 sides
are walls
Limitations on
the height of
the wall
(Refer to 4
side walls)
Front
Front
Front
Front
Front
Front
Front
Front
Front
No limit to the height of the wall
No limit to the
height of the wall
Front
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h
2
= A(Actual height) - 1500
- h
1
= B(Actual height) - 500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
E≥20 E≥100
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
E≥20 E≥100
F≥600 E≥500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥300 D≥100
E≥20 E≥100
F
≥500 E≥500
A≥10
B≥300
A≥200
B≥300
E≥400