Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
- 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number. Indicates unit number.
(* = 1:Master, 2 : Slave 1, 3 : Slave 2)
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
1051 : No.105 error of master unit
h Refer to the DX-Venitilation manual for DX-Venitilation error code
Display Title Cause of Error
Indoor unit related error
0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote controller
↔ indoor unit
Failing to receive wired remote controller signal in indoor unit PCB
0 4 - Drain pump Malfunction of drain pump
0 5 -
Communication error : Indoor communication
PCB ↔ indoor unit
Indoor Unit PCB did not receive signal from Indoor
communication PCB for over 3 minutes continuously
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
0 9 - Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1 0 - Poor fan motor operation
Disconnecting the fan motor connector / Failure of indoor
fan motor lock
2 3 0 Refrigerant leakage sensing error Refrigerant leakage sensing error and sensor defect error
2 3 7
Communication defect in indoor communication
PCB ↔ outdoor communication PCB
Indoor communication PCB did not receive signal from outdoor
communication PCB for over 3 minutes continuously
2 3 8
Communication error in outdoor communication
PCB ↔ outdoor unit
Outdoor communication PCB did not receive communication sig-
nal from outdoor unit for over 3 minutes continuously