Ceiling
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr SavrTM Wireless Occupancy/Vacancy Sensor
369480g 2 10.31.14
Range
LRF2-, LRF3-, LRF4-, LRF5-, LRF7-
Local load controls must be located within 60 ft (18 m)
line-of-sight, or 30 ft (9 m) through walls, of a sensor.
LRF6-
Local load controls must be located within 40 ft (12.2 m)
line-of-sight, or 23 ft (7 m) through walls, of a sensor.
Sensor Coverage Test
Front accessible test button
Lens illuminates orange in response to motion during test
mode and is visible from 60 ft (18 m)
Wireless Communication Test
Front accessible test button
Turn associated loads on and off
Timeout Options
1 minute*
5 minutes
15 minutes (default setting)
30 minutes
Auto-On Options (Occupancy Versions Only)
Enabled: Sensor turns lights ON and OFF automatically
(default setting).
Low Light: Sensor turns lights ON automatically only
in low ambient light conditions; sensor turns lights OFF
automatically.
Disabled**: Lights must be turned ON manually from
dimming or switching device; sensor turns lights OFF
automatically.
Activity Options
Low Activity: (default setting)
Medium Activity:
High Activity:
* Intended for use in high-activity, briefly occupied areas only.
** During the 15-second grace period that begins when the lights are
automatically turned off, the lights will automatically turn back on in
response to motion. This grace period is provided as a safety and
convenience feature in the event the lights turn off while the room is still
occupied, so that the user does not need to manually turn the lights back
on. After 15 seconds, the grace period expires and the lights must be
manually turned on.
Specifications
Regulatory
• Lutron® Quality Systems Registered to ISO 9001:2008
Standards Approved
LRF2- (USA and Canada)
cULus Listed
FCC certified
IC certified
Meets CA (U.S.A.) Energy Commission Title 24
requirements
• COFETEL
• ANATEL
• SUTEL
LRF3-
CE marked (European Union)
TRA type approval (United Arab Emirates)
CITC type approval (Saudi Arabia)
LRF4-
SRRC type approval (Mainland China)
iDA registered (Singpore)
LRF5-
WPC Type (India)
LRF6-
007YUUL0689
LRF7-
• FCC
Power/Performance
Operating voltage: 3 V-
Operating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life
Non-volatile memory (saved changes are stored during
power loss)
Environment
Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
For indoor use only

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lutron Electronics LRF2-OCR2B-P-WH and is the answer not in the manual?

Lutron Electronics LRF2-OCR2B-P-WH Specifications

General IconGeneral
BrandLutron Electronics
ModelLRF2-OCR2B-P-WH
CategoryAccessories
LanguageEnglish

Related product manuals