EasyManuals Logo
Home>Manitowoc>Ice Maker>QY0874C

Manitowoc QY0874C User Manual

Manitowoc QY0874C
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #129 background imageLoading...
Page #129 background image
–125–
SUCTION ACCUMULATOR OPERATION
Liquid refrigerant collects in the suction accumulator
during the harvest cycle and is removed during the
freeze cycle. The liquid refrigerant is returned to the
compressor through a screen and orifice in the suction
accumulator J tube. Passing the liquid through the
orifice causes a pressure drop; the liquid flashes to a
vapor and creates a refrigeration affect. It is normal to
see frost on the accumulator, suction line and
compressor suction port in the freeze cycle. The
suction accumulator empties within the first 5 minutes
of the freeze cycle. When the refrigeration affect ends
(liquid refrigerant has been removed), the suction line
between the accumulator and compressor will
increase in temperature. The suction line temperature
increases 20 plus degrees two minutes after the liquid
has been removed. The time needed to remove the
liquid refrigerant will vary with the ambient
temperature and the length of the harvest cycle.
Higher ambient temperatures = shorter harvest cycles,
faster removal of liquid refrigerant from the
accumulator and greater suction line temperature
increases.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc QY0874C and is the answer not in the manual?

Manitowoc QY0874C Specifications

General IconGeneral
BrandManitowoc
ModelQY0874C
CategoryIce Maker
LanguageEnglish

Related product manuals