EasyManuals Logo
Home>Manitowoc>Ice Maker>SD0452A

Manitowoc SD0452A User Manual

Manitowoc SD0452A
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26 Part Number 80-1479-3 7/10
Calculated Line Set Distance
The maximum calculated distance is 150' (45.7 m).
Line set rises, drops, horizontal runs (or combinations
of these) in excess of the stated maximums will
exceed compressor start-up and design limits. This will
cause poor oil return to the compressor.
Make the following calculations to make sure the line
set layout is within specifications.
1. Insert the measured rise into the formula below.
Multiply by 1.7 to get the calculated rise.
(Example: A condenser located 10 feet above the
ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below.
Multiply by 6.6 to get the calculated drop.
(Example. A condenser located 10 feet below the
ice machine has a calculated drop of 66 feet.)
3. Insert the measured horizontal distance into the
formula below. No calculation is necessary.
4. Add together the calculated rise, calculated
drop, and horizontal distance to get the total
calculated distance. If this total exceeds 150'
(45.7 m), move the condenser to a new location
and perform the calculations again.

Table of Contents

Other manuals for Manitowoc SD0452A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc SD0452A and is the answer not in the manual?

Manitowoc SD0452A Specifications

General IconGeneral
BrandManitowoc
ModelSD0452A
CategoryIce Maker
LanguageEnglish

Related product manuals