Part Number 80-1479-3 7/10 27
Maximum Line Set Distance Formula
Step 1
Measured Rise ____ X 1.7 = ______Calculated Rise
(35 ft. Max)
Step 2
Measured Drop ____ X 6.6 = ______Calculated Drop
(15 ft. Max.)
Step 3
Measured Horizontal Distance = _________Horizontal
(100 ft. Max.) Distance
Step 4
Total Calculated Distance = ________Total Calculated
(150 ft. Max.) Distance
LENGTHENING OR REDUCING LINE SET
LENGTHS
In most cases, by routing the line set properly,
shortening will not be necessary. When shortening or
lengthening is required, do so before connecting the
line set to the ice machine or the remote condenser.
This prevents the loss of refrigerant in the ice machine
or condenser.
The quick connect fittings on the line sets are
equipped with Schraeder valves. Use these valves to
recover any vapor charge from the line set. When
lengthening or shortening lines follow good
refrigeration practices, purge with nitrogen and
insulate all tubing. Do not change the tube sizes.
Evacuate the lines and place about 5 oz (143g) of
vapor refrigerant charge in each line.

Table of Contents

Other manuals for Manitowoc SD0692N

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc SD0692N and is the answer not in the manual?

Manitowoc SD0692N Specifications

General IconGeneral
BrandManitowoc
ModelSD0692N
CategoryIce Maker
LanguageEnglish

Related product manuals