EasyManuals Logo
Home>Manitowoc>Ice Maker>SD0852A

Manitowoc SD0852A User Manual

Manitowoc SD0852A
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Part Number 80-1479-3 7/10 27
Maximum Line Set Distance Formula
Step 1
Measured Rise ____ X 1.7 = ______Calculated Rise
(35 ft. Max)
Step 2
Measured Drop ____ X 6.6 = ______Calculated Drop
(15 ft. Max.)
Step 3
Measured Horizontal Distance = _________Horizontal
(100 ft. Max.) Distance
Step 4
Total Calculated Distance = ________Total Calculated
(150 ft. Max.) Distance
LENGTHENING OR REDUCING LINE SET
LENGTHS
In most cases, by routing the line set properly,
shortening will not be necessary. When shortening or
lengthening is required, do so before connecting the
line set to the ice machine or the remote condenser.
This prevents the loss of refrigerant in the ice machine
or condenser.
The quick connect fittings on the line sets are
equipped with Schraeder valves. Use these valves to
recover any vapor charge from the line set. When
lengthening or shortening lines follow good
refrigeration practices, purge with nitrogen and
insulate all tubing. Do not change the tube sizes.
Evacuate the lines and place about 5 oz (143g) of
vapor refrigerant charge in each line.

Table of Contents

Other manuals for Manitowoc SD0852A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc SD0852A and is the answer not in the manual?

Manitowoc SD0852A Specifications

General IconGeneral
BrandManitowoc
ModelSD0852A
CategoryIce Maker
LanguageEnglish

Related product manuals