Installation Instructions Section 2
6
Part Number 040001361 05/10
Electrical Service
GENERAL
Prepare electrical circuit before installation of your ice
machine. Installation requires a grounded (three-prong),
polarized receptacle with a separate fuse/circuit breaker
in an electrical service box.
VOLTAGE
The maximum allowable voltage variation is ±10% of the
rated voltage at ice machine start-up (when the electrical
load is highest).
All electrical work, including wire routing and grounding,
must conform to local, state and national electrical
codes. The following precautions must be observed:
The ice machine must be grounded.
A separate fuse/circuit breaker must be provided for
each ice machine.
The maximum allowable voltage variation is +/-10%
of the rated voltage at ice machine start-up (when the
electrical load is highest).
Check all green ground screws in the control box and
verify they are tight before starting the ice machine.
Manitowoc’s recommended minimum wire size is
#14 for less than 100' (30.5 m) or #12 for more than
100' to 200' (30.5 to 61 m) (solid copper conductor
only). The recommended breaker is 15 amp. Local or
state electrical code, length of run or materials used,
can increase the minimum wire gauge required. A
qualified electrician must determine the proper wire
size, although #14 is the minimum size allowed.
Incorrect polarity can lead to erratic ice machine
operation and a safety issue.
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select the
wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)
ELECTRICAL REQUIREMENTS
Refer to Ice Machine Model/Serial Plate for voltage/
amperage specifications.
MAXIMUM BREAKER SIZE & MINIMUM CIRCUIT
AMPERAGE CHART
GFCI REQUIREMENTS
If GFCI (ground fault circuit interrupter) is required by
local electrical code, it must be breaker type.
!
Warning
All wiring must conform to local, state and national
codes.
!
Warning
The ice machine must be grounded in accordance
with national and local electrical codes.
Important
Observe correct polarity of incoming line voltage.
Model
Voltage
Phase
Cycle
Air-Cooled
Maximum
Fuse/
Circuit
Breaker
Minimum
Circuit
Amps
SM50A 115/1/60 15 4.1

Table of Contents

Other manuals for Manitowoc SM50 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc SM50 series and is the answer not in the manual?

Manitowoc SM50 series Specifications

General IconGeneral
BrandManitowoc
ModelSM50 series
CategoryIce Maker
LanguageEnglish

Related product manuals