EasyManuals Logo
Home>McQuay>Chiller>MAC 120 C

McQuay MAC 120 C Installation And Maintenance

McQuay MAC 120 C
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Technical Data
Correction Factors With Glycol Use
GLYCOL % COOLING CAPACITY WATER FLOW PRESSURE DROP
10 0.990 1.015 1.06
20 0.980 1.040 1.12
30 0.970 1.080 1.18
40 0.965 1.135 1.24
Water Pressure Drop And Flow Rate
Water Flow Rate Water Pressure Drop
MODEL
L/s m³/h kPa Bar
MAC080C
1.08 3.9 74 0.74
MAC100C
1.31 4.7 82 0.82
MAC120C
1.67 6.0 76 0.76
MAC150C
2.0 7.2 74 0.74
Cooling
1.08 3.9 74 0.74
MAC080CR
Heating
1.14 4.1 72 0.72
Cooling
1.31 4.7 82 0.82
MAC100CR
Heating
1.39 5.0 80 0.80
Cooling
1.67 6.0 76 0.76
MAC120CR
Heating
1.78 6.4 74 0.74
Cooling
2.0 7.2 75 0.45
MAC150CR
Heating
2.11 7.6 73 0.73
Page 20

Other manuals for McQuay MAC 120 C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MAC 120 C and is the answer not in the manual?

McQuay MAC 120 C Specifications

General IconGeneral
BrandMcQuay
ModelMAC 120 C
CategoryChiller
LanguageEnglish

Related product manuals