Doc# M8905 • REV R (May 2016) Page 2 of 8
SUPPLEMENTARY INFORMATION
Refer to product datasheet 1004461, and operaon and maintenance manual 1231558 avail-
able at www.metrixvibraon.com.
MOUNTING
Observe the switch nameplate to ensure that it has the correct hazardous approval and
environmental rangs for the intended area. Refer to Metrix datasheet 1004461 for a list of
all available hazardous area approvals, environmental rangs, and other ordering opons.
See also the Hazardous Area Approvals secon of this manual for hazardous area approvals
informaon.
The switch’s sensive axis is in line with the reset plunger stem. Mount the switch solidly
to the machine’s frame such that this axis is aligned with the direcon of expected vibratory
and/or impact moon. If the machine vibrates along mulple axes (and most machines do),
mount the switch to align with the direcon of highest vibraon. It is typical for machines
to vibrate more in the horizontal direcon than in the vercal direcon, as the foundaon
normally constrains up-and-down moon more than side-to-side moon.
NOTE: The 5550 Mechanical Vibraon Switch is not intended
for use on high-speed turbomachinery or on machines were
changes in seismic acceleraon smaller than 1G must be
reliably detected. Instead, Metrix oers other electronic vibraon
sensing soluons that are beer suited for such applicaons.
NOTE: Do not aempt to measure vibraon or impact perpendicular
to the switch’s sensive axis. The trip plate is free to move along
this axis only and will not respond to moon in other direcons.
of the relay. This relay is available for external wiring connecons where on/o changes in
electrical connuity can be used to trip the machine and/or annunciate excessive vibraon.
Once the switch has assumed its tripped posion, it must be reset manually by means of the
external reset plunger, or by means of an oponal remote electrical reset. The remote reset
capability can also be used as a startup delay to hold the switch in an untripped state for as
long as coil excitaon is supplied – up to 30 seconds (the maximum duraon is governed by
a non-adjustable, factory-installed thermistor circuit). The startup delay feature is useful
during machinery startup when vibraon in excess of the normal trip seng may be tempo-
rarily incurred.