DLFSAB and DLFLAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
DIAGNOSIS AND SOLUTION (CONT.)
EH0E - Water-Level Alarm Malfunction Diagnosis and Solution
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
Connection wires
Water-level switch
Water pump
Indoor PCB
Troubleshooting and Repair:
Power off, then rest art t he unit 2 minut es
later.
Is the water-level switch
inserted properly?
Insert the w ater-level sw it ch
properly
NO
YES
Replace the wat er-level switch
NO
YES
Replace the indoor main PCB
Does a problem
remain?
YES
The unit is operating normally.
NO
Is the water level
switch broken?