MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
Troubleshooting 95
5.2 E1: Phase sequence error (Display on faulty unit, all the ODU in standby)
Note:
If the wiring connection of each outdoor unit is according to A, B, C phase sequence, when the quantity of
outdoor units is large, the current difference between C phase and A, B phase will be very large for the
power supply load of each outdoor unit is on C phase, it is very easy to lead to air switch break and wiring
terminal burnout. So when the quantity of outdoor units is large, the phase sequence should be staggered,
then the current can be distributed to the three phases equally.
E1: Phase sequence error
The 3-phase sequence of power supply
is
wrong. (The A, B, C terminal of three-phase
power supply should meet compressor phase
sequence requirement. If the phase
sequence is adverse, the compressor will
operate inversely.
Exchange any two of the
3-sequence
Some power supply terminals are
loose, if there has phase loose, the
compressor will operate abnormally,
and the current is very large
Fasten each phase joint of
power supply.
MC9S08AC128 chip is disabled
Main board is disabled
Replace main board
No
No
No
Yes
Yes
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MDV-900W/DRN1-i(C) and is the answer not in the manual?

Midea MDV-900W/DRN1-i(C) Specifications

General IconGeneral
BrandMidea
ModelMDV-900W/DRN1-i(C)
CategoryAir Conditioner
LanguageEnglish

Related product manuals