Specification MCAC-TSM-2008-02
20 Installation
6. Electric Characteristics
Outdoor Unit Power Supply Compressor OFM
Model
Hz Voltage phase Min. Max. MCA TOCA MFA MSC RLA kW FLA
MGC-F05W/N1 50Hz 220-240V 1ph 198V 254V 11.25 10.8 15 36.8 8.7 0.12 1
MGC-F07W/N1 50Hz 220-240V 1ph 198V 254V 17.5 16.6 20 63 13.1 0.12 1
MGC-F09W/N1 50Hz 220-240V 1ph 198V 254V 24.5 32 35 123 19.5 0.1×2 0.8×2
MGC-F10W/N1 50Hz 220-240V 1ph 198V 254V 24.5 32 35 123 19.5 0.1×2 0.8×2
MGC-F10W/SN1 50Hz 380-415V 3ph 342V 440V 9.2 10.5 20 64 7.3 0.1×2 0.8×2
MGC-F12W/SN1 50Hz 380-415V 3ph 342V 440V 12.12 11.5 15 66 8.22 0.1×2 0.8×2
MGC-F14W/SN1 50Hz 380-415V 3ph 342V 440V 10.2 25 15 67 9.77 0.1×2 0.8×2
MGC-F16W/SN1 50Hz 380-415V 3ph 342V 440V 15.75 15 20 73 11.6 0.1×2 0.8×2
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Current Amps. (A)
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A)
kW: Rated Motor Output. (kW)