Midea M thermal Mono Service Manual
1 Stop Operation
The stop operation occurs for one of the following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off operation and an error code is displayed on the outdoor unit PCB digital displays and on the user
interface.
2. The system stops when the set temperature has been reached.
2 Standby Control
2.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped.
The crankcase heater is controlled according to outdoor ambient temperature and the compressor on/off state. When the
outdoor ambient temperature is above 8°C or the compressor is running, the crankcase heater is off; when the outdoor
ambient temperature is at or below 8°C and either the compressor has been stopped for more than 3 hours or the unit has
just been powered-on (either manually or when the power has returned following a power outage), the crankcase heater
turns on.
2.2 Water Pump Control
When the outdoor unit is in standby, the internal and external circulator pumps run continuously.
Midea CAC Confidential

Other manuals for Midea MHC-V4W/D2N8-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V4W/D2N8-B and is the answer not in the manual?

Midea MHC-V4W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V4W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals