Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the
compressor frequency will rise to the higher
level. (The frequency will increase twice at
most)
8.4.3.2 Outdoor fan running rules
8.4.3.3 Indoor fan running rules
Indoor fan speed can be set as high, medium,
low, silent mode or auto grade. During all the
fan speeds, the anti-cold-wind function is
preferential. If the compressor stops caused by
the room temperature rising, the indoor fan will
run at super breeze. When the compressor is
running, the indoor fan is controlled as below:
The anti-cold wind function is as below:
For MS11M-09HRFN1-MW0W,
MS11M-12HRFN1-MV0W,
MS11M-18HRFN1-MU0W models: