EasyManuals Logo
Home>Midea>Air Conditioner>MSG-09CR

Midea MSG-09CR User Manual

Midea MSG-09CR
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Service manual
- 25 -
8.7 Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valves service port.
§ Leave the valve on the charge set closed.
§ Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge
indicates 0.05 to 0.1 Mpa.
§ If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is
higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the
case, it will not be necessary to apply a evacuation.
§ Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be
discharged.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MSG-09CR and is the answer not in the manual?

Midea MSG-09CR Specifications

General IconGeneral
BrandMidea
ModelMSG-09CR
CategoryAir Conditioner
LanguageEnglish

Related product manuals