VC Pro VRF 50/60Hz
47
Part 2 - Outdoor Unit Engineering Data
6 Electrical Characteristics
Table 2-6.1: Outdoor unit electrical characteristics
Model
Power Supply
1
Compressor
OFM
Capacity
Modules
Hz
Volts
Min.
volts
Max.
volts
MCA
2
TOCA
3
MFA
4
MSC
5
RLA
6
kW
FLA
8HP
50/60
380~415
342
456
24
29.4
32
/
10
0.56
2.1
10HP
50/60
380~415
342
456
24.5
29.4
32
/
11.1
0.56
2.1
12HP
50/60
380~415
342
456
24.7
29.4
32
/
14.8
0.56
2.1
14HP
50/60
380~415
342
456
29.7
36.3
40
/
26
0.75
2.5
16HP
50/60
380~415
342
456
30.3
36.3
40
/
26.5
0.75
2.5
18HP
50/60
380~415
342
456
45
56.8
50
/
16+15
0.56×2
2.2
20HP
50/60
380~415
342
456
45.5
56.8
50
/
19+18
0.56×2
2.2
22HP
50/60
380~415
342
456
46
56.8
50
/
20+19
0.56×2
2.2
24HP
50/60
380~415
342
456
57
71.7
63
/
20.9+19.8
0.56×2
5.1
26HP
50/60
380~415
342
456
57.8
71.7
63
/
21.2+20.5
0.56×2
5.1
28HP
50/60
380~415
342
456
58.3
71.7
63
/
26+25
0.56×2
5.1
30HP
50/60
380~415
342
456
58.8
71.7
63
/
27+26
0.56×2
5.1
32HP
16HP
16HP
50/60
380~415
342
456
60.6
72.6
40+40
/
26.5+26.5
0.75*2
5
34HP
12HP
22HP
50/60
380~415
342
456
70.7
86.2
32+50
/
14.8+20+19
0.56*3
4.3
36HP
16HP
20HP
50/60
380~415
342
456
75.8
93.1
40+50
/
26.5+19+18
0.75+0.56*2
4.7
38HP
16HP
22HP
50/60
380~415
342
456
76.3
93.1
40+50
/
26.5+20+19
0.75+0.56*2
4.7
40HP
16HP
24HP
50/60
380~415
342
456
87.3
108
40+63
/
26.5+20.9+19.8
0.75+0.56*2
7.6
42HP
16HP
26HP
50/60
380~415
342
456
88.1
108
40+63
/
26.5+21.2+20.5
0.75+0.56*2
7.6
44HP
16HP
28HP
50/60
380~415
342
456
88.6
108
40+63
/
26.5+26+25
0.75+0.56*2
7.6
46HP
16HP
30HP
50/60
380~415
342
456
89.1
108
40+63
/
26.5+27+26
0.75+0.56*2
7.6
48HP
22HP
26HP
50/60
380~415
342
456
103.8
128.5
50+63
/
20+19+21.2+20.5
0.56*4
7.3
50HP
22HP
28HP
50/60
380~415
342
456
104.3
128.5
50+63
/
20+19+26+25
0.56*4
7.3
52HP
22HP
30HP
50/60
380~415
342
456
104.8
128.5
50+63
/
20+19+27+26
0.56*4
7.3
54HP
26HP
28HP
50/60
380~415
342
456
116.1
143.4
63+63
/
21.2+20.5+26+25
0.56*4
10.2
56HP
28HP
28HP
50/60
380~415
342
456
116.6
143.4
63+63
/
26+25+26+25
0.56*4
10.2
58HP
28HP
30HP
50/60
380~415
342
456
117.1
143.4
63+63
/
26+25+27+26
0.56*4
10.2
60HP
30HP
30HP
50/60
380~415
342
456
117.6
143.4
63+63
/
27+26+27+26
0.56*4
10.2
62HP
16HP
16HP
30HP
50/60
380~415
342
456
119.4
144.3
40+40+63
/
26.5+26.5+27+26
0.75*2+0.56*2
10.1
64HP
16HP
22HP
26HP
50/60
380~415
342
456
134.1
164.8
40+50+63
/
26.5+20+19+21.2+20.5
0.75+0.56*4
9.8
66HP
16HP
22HP
28HP
50/60
380~415
342
456
134.6
164.8
40+50+63
/
26.5+20+19+26+25
0.75+0.56*4
9.8
68HP
16HP
22HP
30HP
50/60
380~415
342
456
135.1
164.8
40+50+63
/
26.5+20+19+27+26
0.75+0.56*4
9.8
70HP
16HP
26HP
28HP
50/60
380~415
342
456
146.4
179.7
40+63+63
/
26.5+21.2+20.5+26+25
0.75+0.56*4
12.7
72HP
16HP
28HP
28HP
50/60
380~415
342
456
146.9
179.7
40+63+63
/
26.5+26+25+26+25
0.75+0.56*4
12.7
74HP
16HP
28HP
30HP
50/60
380~415
342
456
147.4
179.7
40+63+63
/
26.5+26+25+27+26
0.75+0.56*4
12.7
76HP
16HP
30HP
30HP
50/60
380~415
342
456
147.9
179.7
40+63+63
/
26.5+27+26+27+26
0.75+0.56*4
12.7
78HP
22HP
28HP
28HP
50/60
380~415
342
456
162.6
200.2
50+63+63
/
20+19+26+25+26+25
0.56*6
12.4
80HP
22HP
28HP
30HP
50/60
380~415
342
456
163.1
200.2
50+63+63
/
20+19+26+25+27+26
0.56*6
12.4
82HP
22HP
30HP
30HP
50/60
380~415
342
456
163.6
200.2
50+63+63
/
20+19+27+26+27+26
0.56*6
12.4
84HP
28HP
28HP
28HP
50/60
380~415
342
456
174.9
215.1
63+63+63
/
26+25+26+25+26+25
0.56*6
15.3
86HP
28HP
28HP
30HP
50/60
380~415
342
456
175.4
215.1
63+63+63
/
26+25+26+25+27+26
0.56*6
15.3
88HP
28HP
30HP
30HP
50/60
380~415
342
456
175.9
215.1
63+63+63
/
26+25+27+26+27+26
0.56*6
15.3
90HP
30HP
30HP
30HP
50/60
380~415
342
456
176.4
215.1
63+63+63
/
27+26+27+26+27+26
0.56*6
15.3
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Full
Load Amps
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage
variation between phases is 2%.
2. Select wire size based on the value of MCA.
3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.