VC Pro VRF 50/60Hz
152
Midea VC Pro Series Engineering Data Book
4 Refrigerant Piping Design
4.1 Design Considerations
Refrigerant piping design should take account of the following considerations:
The amount of brazing required should be kept to a minimum.
On the two inside sides of the first indoor branch joint (A in Figures 3-4.2, 3-4.3 and 3-4.4) the system should, as far
as possible, be equal in terms of number of units, total capacities and total piping lengths.
4.2 Material Specification
Only seamless phosphorus-deoxidized copper piping that complies with all applicable legislation should be used. Temper
grades and minimum thicknesses for different diameters of piping are specified in Table 3-4.1.
Table 3-4.1: Piping temper and thickness
Piping outer
diameter
(mm)
Temper
Minimum thickness
(mm)
Ф6.35
M-type
0.8
Ф9.53
0.8
Ф12.7
1.0
Ф15.9
1.0
Ф19.1
1.0
Ф22.2
Y2-type
1.0
Ф25.4
1.0
Ф28.6
1.0
Ф31.8
1.25
Ф34.5
1.25
Ф38.1
1.5
Ф41.3
1.5
Ф44.5
1.5
Ф50.8
1.8
Ф54.0
1.8

Questions and Answers: