VC Pro VRF 50/60Hz
15
Part 1 - General Information
Table 1-6.2: Extract from medium static pressure duct (T2) cooling capacity table
Abbreviations:
TC: Total capacity (kW); SHC: Sensible heat capacity (kW)
Table 1-6.3: Selected indoor units
Step 3: Select outdoor units
Determine the required total heat load from the indoor units to the outdoor units based on either the sum of the
peak loads of each room or the system peak load. In this example, it is determined based on the system peak load.
Therefore, the required heat load is 50.7kW.
Provisionally select outdoor units using the sum of the capacity indexes (CIs) of the selected indoor units (as shown in
Table 1-6.4), ensuring that the combination ratio is between 50% and 130%. Refer to Table 1-6.5. As the sum of CIs of
the indoor units is 706, outdoor units from 20HP to 50HP are potentially suitable. Start from the smallest, which is the
20HP unit.
Table 1-6.4: Sum of indoor unit capacity indexes